Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC3100
92
Manual, 07/2009, A5E02385159B-01
Data bits / Parity bits / Stop bits
Range:
8N2, 8E1, 8O1, 8N1
FORMAT
Default
value:
8N2
Response time
Range:
0 to 255 ms
0 = Auto
RESPONSE TIME
Default
value:
0
You can find the function codes for access via the RS 485 interface in the Appendix.
See also
RS 485 interface (Page 26)
Modbus RTU (Page 125)
9.2.9
Display
Device settings for the SENTRON PAC3100 display.
Call: "SETTINGS > DISPLAY"
Figure 9-9
"DISPLAY" device setting
Device settings of the display
CONTRAST
Contrast of the LC display.
Range: 0 to 10.
Default value: 5
BACKLIGHT LEVEL
Backlighting of the LC display.
ON/OFF switch: ON / OFF.
OFF: Backlighting switched off
On: Backlighting switched on
Default value: ON.
Note: Switching the backlighting off increases the service
life of the display. To achieve a service life of more than
10 years, the backlighting should be switched on no more
than 10% of the device operating time.
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...