Technical data
11.1 Technical data
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
107
Digital inputs
Number
2
Type
Internal power supply
External operating voltage
0 ... 30 V DC (optional)
Contact resistor
"1" signal detection
≤ 1 kΩ
"0" signal detection
≥ 100 kΩ
Input current
"1" signal detection
2.5 … 10 mA
"0" signal detection
≤ 0.5 mA
Digital outputs
Number
2
Type
Bidirectional
Design/function
Switching output or pulse output
Rated voltage
0 ... 30 V DC, typical 24 V DC
(SELV or PELV supply)
Output current
For signal "1"
Depends on the load and the external power
supply
Continuous load
≤ 50 mA (thermal overload protection)
Transient overload
≤ 130 mA for 100 ms
For signal "0"
≤ 0.2 mA
Internal resistance
55 Ω
Overvoltage category
CAT I
Pulse output function
Standard for pulse emitter
Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration
30 … 500 ms
Min. settable time frame
10 ms
Max. switching frequency
17 Hz
Short-circuit protection
Yes
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...