Commissioning
7.6 Checking the displayed measured values
SENTRON PAC3100
62
Manual, 07/2009, A5E02385159B-01
Direction of current flow
Please take account of the direction of current flow when connecting the current measuring
inputs. With inverse connection, the measured values are inverted and receive a negative
sign.
To correct the direction of current flow, it is not necessary to reverse the input terminals.
Instead, change the interpretation of the direction in the device settings.
You can find more information in the chapter "Basic parameters", "CURRENT DIREC" fields.
See also
Measuring inputs (Page 17)
Safety notes (Page 13)
Safety notes (Page 39)
Basic parameters (Page 85)
7.6
Checking the displayed measured values
Correct connection type
With the help of the table "Displaying the measured variables depending on the connection
type", check whether the measured variables are displayed in accordance with the
connection type executed. Any deviation indicates a wiring fault or configuration error.
See also
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...