Commissioning
7.3 Parameterizing the device
SENTRON PAC3100
56
Manual, 07/2009, A5E02385159B-01
7.
Open edit mode of the "CONNECTION TYPE" device setting:
<F4>
8.
Scroll through the possible values with:
<F2>
9.
Accept the desired connection type:
<F4>
The connection type is permanently saved and becomes effective immediately.
The display returns to display mode.
10.
Return to one of the selection menus or to the measured values display:
<F1>
See also
7.3.2.2
Measurement using voltage transformers
The factory setting is measurement direct on the system. At initial startup, the following steps
must be carried out if you want to measure using voltage transformers.
Procedure
1.
In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2.
In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
3.
Go to the "USE PTs?" device setting:
<F2>
or <F3>
Figure 7-5
"USE PTs?" device setting
4.
Switch converter measurement on/off:
<F4>
On: Measurement using voltage transformers.
Off: Measurement direct on the low-voltage system.
The device setting is saved permanently and becomes effective immediately.
The display remains in display mode.
5.
Return to one of the selection menus or to the measured values display:
<F1>
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...