Operation planning
SENTRON PAC3100
30
Manual, 07/2009, A5E02385159B-01
Environmental conditions
Use the SENTRON PAC3100 device only where environmental conditions permit its
operation:
Table 4- 1
Environmental conditions
Temperature range
Operating temperature
- 10 °C t 55 °C
Storage and transport temperature
- 25 °C t 70 °C
Relative humidity
95% at 25°C without condensation (normal
conditions)
Installation altitude above sea level
max. 2000 m
Degree of pollution
2
Degree of protection according to IEC 60529
Device front
IP65
Type 5 enclosure acc. to UL50
Device rear
IP20
Circuit breaker
A suitable circuit breaker must be connected upstream of SENTRON PAC3100 in order to
permit disconnection of the device from the power supply!
●
The circuit breaker must be mounted close to the device and be easily accessible to the
user.
●
The circuit breaker must be marked as the circuit breaker for the device.
Temperature compensation
To avoid condensation, the device must be stored at the operating location for at least 2
hours before power is connected.
See also
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...