Connection
6.5 Connecting to the RS 485 bus
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
49
RS 485 terminal block
COM
Common = Ground
+/B
B signal; D1
-/A
A signal; D0
Figure 6-11 RS 485 terminal block
Block diagram
7(5
7(5
'
5
6ODYH
'
5
6ODYHQ
%DODQFHG3DLU
'
'
'
5
0DVWHU
9
SXOOXS 38
SXOOGRZQ 3'
%
$
&RPPRQ
TER
Bus termination resistor (termination)
PU
Pull-up resistor
PD
Pull-down resistor
(1)
Grounding of the cable shielding
(2)
Grounding of the common line, preferably only at one point for the whole bus
Figure 6-12 Block diagram: General RS 485 topology