Commissioning
7.2 Applying the supply voltage
SENTRON PAC3100
52
Manual, 07/2009, A5E02385159B-01
Supply voltage fuse protection
CAUTION
Non-fused supply voltage may lead to device and equipment damage
Always protect the device with an IEC approved or UL listed CLASS CC 0.6 A fuse.
If a fusible link is used, a suitable IEC approved or UL listed fuse holder has to be used. In
addition, a suitable isolating device shall be connected upstream in order to permit
disconnection of the device from the power supply.
Do not use voltage transformers as a power supply.
Procedure
Connect the supply voltage to terminals L/+ and N/-.
Table 7- 1
Connection of supply voltage
Terminal marking
Connection
L/+
AC: Connection: Conductor (phase-to-neutral voltage)
DC: Connection: +
N/-
AC: Connection: Neutral conductor
DC: Connection: -
See also
Safety notes (Page 13)
Safety notes (Page 39)
Applying the measuring voltage (Page 60)
Technical data (Page 105)
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...