Technical data
11.1 Technical data
SENTRON PAC3100
106
Manual, 07/2009, A5E02385159B-01
Measuring inputs for current
Only for connection to AC power systems via external current transformers
Input current I
I
x / 5 A 3 AC (+ 20%)
Max. permissible continuous current
10 A
Current impulse overload capability
100 A for 1 s
Zero point suppression level
throughout phases
10 mA
in the neutral conductor
45 mA
Max. power consumption per phase
500 mVA at 6 A
Measuring accuracy
Measured variable
Accuracy class in accordance with
IEC 61557-12:2007-08 (K55)
Voltage
1
Current
1
Apparent power
1
Active power
1
Reactive power
3
Total apparent power over all phases
1
Total active power over all phases
1
Total reactive power VAR1 over all phases
3
Cumulated active power
1
Cumulated reactive power
3
Total power factor
2
Line frequency
0,1
Active energy
1
Reactive energy
3
When measuring on external current transformers or voltage transformers, the accuracy of
the measurement depends on the quality of the transformer.
Power supply
Design of the power supply
Wide-range power supply AC / DC
Rated range
100 … 240 V AC (45 … 65 Hz) or
110 … 250 V DC
Work area
± 10% of AC/DC rated range
Power consumption
5 W DC / 10 VA AC
Overvoltage category
CAT III
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...