Page 46
Pointek CLS500 – INSTRUCTION MANUAL
7ML19985GG03
mmm
mm
St
a
rt
u
p
Start-up: Pointek CLS500
Capacitance measurement systems require the instrument to be adjusted for a particular
application. Two methods of adjustment are available:
• push-button (for instructions, see page 51)
• HART (for instructions, see page 54)
Quick Start
We strongly recommend you read the full manual to use your Pointek CLS500 to its fullest
potential. However, if you can bring the product to the 0% and 100% point level, you can
use the Quick Start sequence on page 47 to set up the instrument and get started. (For
most applications, 0% is an uncovered probe, and 100% is a covered probe.)
Pointek CLS500 is most often used in Failsafe High or Failsafe Low mode (FSH or FSL),
which sets the loop current to 4 or 20 mA 2-state mode.