Appendix A
The transmitter variable on which this selection is based is chosen in Menu 01. The
increment/decrement step size is set at Menu 09.
To set overfill protection
1
, first set LRV at menu 0E, then:
1. Set the rotary switch to D.
2. Press and hold both buttons simultaneously to take the minimum span as Delta
value.
or: Press the RED (+) or BLUE (–) button to increase or decrease the value.
or: Press and hold a button to start a repeat function.
Lower Range Value
Lower Range Value (LRV) is the setting for 0% of the operating range, in most cases an
empty vessel/tank. (If the display mode is in %
2
this selection is disabled and the LCD
displays - - - -.)
The transmitter variable on which this menu selection operates is chosen in Menu 01. The
factory setting is TV0.
The increment/decrement step size is subject to the setting from Menu 09.
1. Set the rotary switch to E.
2. Press and hold both buttons simultaneously to take the current PV reading as
the new setting.
or: Press the RED (+) or BLUE (–) button to step the value up or down.
or: Press and hold a button for a prolonged time to start a repeat function.
When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value
is rejected and the previous value remains unchanged.
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Description
Values
0D
01, 07, 09
D
Off
2-state
Delta Range Setting
enabled
Span
(pF)
*
330
Analog
Display
shows
- - - -
1.
For more details, see
Delta Range Setting application
2.
This option is available but not useful for Pointek CLS500.
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Description Values
0E
01, 09, 0B,
0C
E
Off
Analog
Lower Range
Value
Range: 0.00 to 330
2-state *
0.00