Page 80
Pointek CLS500 – INSTRUCTION MANUA
7ML19985GG03
mmmmm
Appendix A
Factory Settings
Displays whether the factory settings are still in place, or how much they have been
changed, and allows you to restore the factory settings.
Set the rotary switch to 2. To restore the factory settings, press both buttons
simultaneously to change the LCD to ‘do it’ and hold both buttons for more than one
second. When the buttons are released, the LCD displays FAC A.
Range Inversion
Displays whether the device is operating with a normal or inverted range setting.
A normal range setting is where LRV (Menu 0E) is lower in value than URV (Menu 0F): the
LCD displays nor. An inverted range is where LRV (Menu 0E) is higher in value than URV
(Menu 0F): the LCD displays inv.
1. Set the rotary switch to 9.
2. Press both buttons simultaneously for more than one second to toggle between
the two modes, effectively switching the values for LRV and URV.
Menu
Item
Rotary
Switch
Position
Left Arrow
Description
LCD
Display
Meaning
12
2
On
Factory Settings
FAC A
No parameters
changed from factory
setting
FAC P
Range settings altered:
timers and thresholds
unchanged
FAC ?
More parameters have
been changed
Menu
Item
Rotary
Switch
Position
Left Arrow
Description
Mode
Values
19
9
On
Range Inversion
normal
*
Display shows nor
inverted
Display shows inv