Page 64
Pointek CLS500 – INSTRUCTION MANUA
7ML19985GG03
mmmmm
Appendix A
Upper Sensor Limit
The Upper Sensor Limit (USL) is the upper of two limit settings. Whenever the PV value
(Menu Level 0) rises above the upper limit setting, the measurement is considered at fault
and the LCD displays ooL, alternating with PV.
(If the display mode is in %
1
, this selection is disabled and the LCD displays - - - -.) The
transmitter variable on which this menu selection operates is chosen in Menu 01.
The increment/decrement step size is subject to the setting from Menu 09.
1. Set the rotary switch to C.
2. Press the RED (+) or BLUE (–) button to increase or decrease this value.
or: Press and hold a button to start a repeat function.
or: Press and hold both buttons simultaneously to take the current PV reading as
the new setting.
Delta Range Setting
The Delta Range Setting allows you to commission the unit for overfill or underfill
protection where it is impossible to bring the product to those levels in normal process
conditions. The default value is the span between URV and LRV, but when you apply Delta
Range Setting, it applies the minimum span (1.0 pF).
Overfill protection is used in applications where the probe is normally uncovered. Delta
Range Setting adds the minimum span to the Lower Range Value: the result is used to
update the Upper Range Value. If the process level exceeds the new URV, a fault is
signalled.
Underfill protection would be used in applications where the probe is normally covered.
In this case, Delta Range Setting subtracts the minimum span from the Upper Range
Value and uses the result to update the Lower Range Value. If the process value drops
below the new LRV, a fault is signalled.
The loop-current control must be in 2-state mode
2
(Menu 07) for Menu 0D to display the
Delta Range Setting. If the loop-current control is in Analog mode, Menu 0D displays - - - -.
1.
This option is available but not useful for Pointek CLS500.
Menu
Item
Affected
by:
Rotary
Switch
Position
Left Arrow Description
Values
0C
01, 09
C
Off
Upper Sensor Limit
330 to 0
Factory setting
330
2.
The default mode for Pointek CLS500 is FailSafe High (set at menu 1E): this sets menu
07 to 2-state mode, and menu 08 to FailSafe High. Only if Pointek CLS500 is used in
Free Programming Mode can Analog mode be selected at menu 07.