Appendix A
Lower Threshold Delay (2-state mode)
The Lower Threshold Delay controls the Deactivation delay: the amount of time that has
to pass uninterrupted with the probe covered to a level below the Lower Threshold
Setting before the timer expires. When the timer expires, the output signal will comply
with the setting from Menu 08 for an uncovered probe. Whenever the level rises above
the Lower Threshold Setting before the timer expires, the timer is restarted.
As an extra identifier, a downward running A is displayed to the right of the value.
1. Set the loop-current control (Menu 07) to 2-state mode.
2. Set the rotary switch to 4.
3. Press the RED (+) or BLUE(–) buttons to increase or decrease the value.
or: Press and hold a button to start a repeat function.
or: Press and hold both buttons simultaneously to toggle the value between
minimum (0) and maximum (100).
Upper Threshold Setting (2-state mode)
The Upper Threshold Setting is the % of range above which the probe is considered
covered. In order to switch the output signal, the corresponding delay time has to be met
(Menu 03).
The loop-current control (Menu 07) must be in 2-state mode for this menu to display the
Upper Threshold Setting in percent. As an extra identifier, an upward ramp is
displayed to the right of the value.
1. Set the loop-current control (Menu 07) to 2-state mode.
2. Set the rotary switch to 5.
3. Press the RED (+) or BLUE (–) button to increase or decrease the value.
or: Press and hold a button to start a repeat function.
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Added
Indicator
Des-
cription
Values
04
07
4
Off
2-state
*
Downward
running A to
right of value
Lower
Threshold
Delay
seconds
factory setting
0.0
Analog
Display
shows
- - - -
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Added
Indicator
Description Values
05
07
5
Off
2-state
*
Upward
ramp at right
of value
Upper
Threshold
Setting
% of
range
factory setting
75
Analog
Display
shows
- - - -