
Page 66
Pointek CLS500 – INSTRUCTION MANUA
7ML19985GG03
mmmmm
Appendix A
Upper Range Value
Upper Range Value (URV) is the setting for 100% of the operating range, in most cases a
full vessel/tank. (If the display mode is in %
1
this selection is disabled and the LCD
displays - - - -.)
The transmitter variable on which this menu selection operates is chosen in Menu 01, and
the factory setting is TV0.
The increment/decrement step size is subject to the setting from Menu 09.
1. Set the rotary switch to F.
2. Press and hold both buttons simultaneously to take the current PV reading as
the new setting.
or: Press the RED (+) or BLUE (–) button to step the value up or down.
or: Press and hold a button for a prolonged time to start a repeat function.
When the new setting exceeds that of the Limit Settings (Menu 0C and 0B), the new value
is rejected, and the previous value remains unchanged.
Transmitter Variable Values: menu level 0
Dynamic Value, Primary Variable (PV): menu 00 and menu 10
The value for the Primary Variable is displayed as either units (or percent of range
selected in menu 01. In Fail Safe mode (the factory setting) 2-state mode is selected in
menu 07 and the LCD display indicates the probe status:
• blinking for an uncovered probe
• steady for a covered probe
If the internal diagnostics detect a fault or failure, the display alternates between the PV
value and the fault/failure message ‘Flt’. If the product level goes outside the limit settings,
then the display alternates between the PV value and ‘ooL’. Alternatively, if the simulation
(SIM) function has been selected via HART, the LCD alternately displays the text SIM or
the applied simulation value for the duration of the simulation.
1.
This option is available but not useful for Pointek CLS500.
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Description Values
0F
01, 09, 0B,
0C
F
Off
Analog
Upper Range
Value
Range: 330 to 0
2-state
*
330
Note:
Menus 00 and 10 are the only locations where you can change from level 1 to
level 0, or vice versa.