Page 54
Pointek CLS500 – INSTRUCTION MANUAL
7ML19985GG03
mmm
mm
St
a
rt
u
p
Setup using HART
You can set up Pointek CLS500 transmitter using HART, with a HART communicator; a
laptop running Simatic PDM, or with the Host system (DCS). The local circumstances
determine the easiest method. If you can bring the product to the 0% and 100% point
level, setup is simple. (Either the probe state is uncovered at 0%, and covered at 100%,
or the reverse.)
Examples of set up using a Rosemount 275 hand-held communicator, fitted with the
GENERIC device descriptor:
Example 1
For situations where the level of the product can be easily adjusted to 0 and 100%.
First install Pointek CLS500, then power it up: the probe must be uncovered.
1.
Switch on the 275 and request connection with Pointek CLS500.
a. Select: Online
b. Select: Device setup
c. Select: Diag service
d. Select: Calibration
e. Select: Apply values
(Display reads: Loop should be removed from automatic control. Select: Ok)
f. Select: 4 mA
g. Select: Apply new 4 mA input
2.
Bring the level of the product to the level which corresponds with 4 mA.
a. Select: Read new value
b. Select: Set as 4 mA value: the 4 mA point has now been set.
c. Select: 20 mA
d. Select: Apply new 20 mA input
3.
Bring the level of the product to the level which corresponds with 20 mA.
a. Select: Read
new
value
b. Select: Set as 20 mA value: the 20 mA point has now been set.
c. Select: Exit
(Display reads: Loop may be returned to automatic control. Select: Ok)
Setup is complete.
Notes:
•
Use the arrow keys, up, down, forward, and back to navigate within the menus.
•
Use the back arrow to return to previous screens.