38/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
6 Function
29.11.2011
6 Function
6.1 Preconditions for burner startup
Burner control must be reset
All contacts in the line are closed, there is a request for heat
No
undervoltage
Air pressure switch or POC must be in its no-load position, or Dbr1 is connected to
X2-02 (depending on program sequence)
Flame detector is darkened and there is no extraneous light
All contacts in the safety loop are closed
6.2 Undervoltage
Safety shutdown from the operating position takes place should mains voltage drop
below about AC 75 V (UN = AC 120 V)
Restart is initiated when mains voltage exceeds about AC 100 V (UN = AC 120 V)
Safety shutdown from the operating position takes place should mains voltage drop
below about AC 165 V (UN = AC 230 V)
Restart is initiated when mains voltage exceeds about AC 195 V (UN = AC 230 V)
6.3 Controlled
intermittent
operation
Depending on parameter 239, after no more than 24 hours of continuous operation, the
burner control initiates automatic controlled shutdown followed by a restart, against
parameter 239.