23 Operation via AZL2…
29.11.2011
23.4.1.4.
Fault status messages, display of errors and info
Display of errors (faults) with lockout
P
V
h min s
%
Bi
ld
1
8
5/
11
0
7
Display shows
Loc:
. The bar under the fault status
message
appears.
Unit is in the lockout position.
The current error code is displayed (see chapter
Blink
code table
).
Example: Error code
7
Reset
/reset
1 s
P
V
h min s
%
B
ild
1
9
/0
70
7
When pressing
/reset
for 1 second,
rESEt
appears on the
display.
When the button is released, the basic unit is reset.
/reset
< 3 s
P
V
h min s
%
B
ild
2
0
/0
70
7
P
V
h min s
%
B
ild
2
1
/0
70
7
P
V
h min s
%
B
ild
2
2
/0
70
7
When pressing
/reset
for
>
3 seconds, the display shows
InFo
,
SEr
and then
OPErAtE
.
When the button is released, the basic unit is reset.
Note:
For meaning of the error and diagnostic codes, see chapter
Error code list…
When an error has been acknowledged, it can still be read out from the error history.