27 PWM settings
29.11.2011
Parameter
number
516
blinks. Press
to select the next parameter. Parameter
517
blinks
Now, for the following parameters, proceed as described above:
-
P1
low-fire
position
517
-
P2
high-fire
position
518
For parameter number
519
, press
/reset
for >1 second
By
pressing or
the speed can be changed in step sizes of 10 rpm. Also
see chapter
Setting parameters without index, without direct display.
Set the
required maximum speed for the connected fan (also see the supplier’s Data
Sheet)
Press
/reset
to transfer the setting value to onboard memory
By
pressing
ESC
(press
and
simultaneously) you leave the entry level
and return to the selection level for the parameters
Parameter
number
519
blinks. Press
to select the next parameter. Parameter
644
blinks
Press
/reset
for >1 second
By
pressing or
the number of pulses per revolution (Hall signals) the unit
feeds back to the control can be set (see supplier’s Data Sheet)
Press
/reset
to transfer the setting value to the onboard memory
By
pressing
ESC
(press
and
simultaneously) you leave the entry level
and return to the selection level for the parameters
Parameter
number
644
blinks. Press
to select the next parameter. Parameter
P0
blinks
By
pressing
A
(display changes to
0A
and speed appears blinking) and pressing
or
the speed can be changed within the predefined limits (
P0
max,
P0
min)
in step sizes of 10 rpm
Press
/reset
to transfer the setting value to the onboard memory and the next
parameter
P1
By
pressing
A
(display changes to
1A
and speed appears blinking) and pressing
or
the speed can be changed within the predefined limits (P1max, P1min)
in step sizes of 10 rpm
Press
/reset
to transfer the setting value to the onboard memory and the next
parameter
P2
By
pressing
A
(display changes to
2A
and speed appears blinking) and pressing
or
the speed can be changed within the predefined limits (P2max, P2min)
in step sizes of 10 rpm
Press
/reset
to transfer the setting value to the onboard memory and to complete
the initial settings
Display
shows
-END-