30/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
4 Technical data
29.11.2011
4 Technical
data
4.1 Basic unit LME7...
Mains voltage
AC 120 V
AC 230 V
Mains frequency
50/60 Hz
50/60 Hz
External primary fuse
Max. 6.3 A (slow)
Max. 6.3 A (slow)
Power consumption
<10 W, typical
<10 W, typical
Safety class
I with parts according to II and III to
DIN EN 60730-1
IP00
Degree of protection
Note:
The burner or boiler
manufacturer must ensure
degree of protection IP40 for
burner controls as per DIN EN
60529 through adequate
installation of the LME7...
Perm. mounting position
Optional
Weight
Approx. 490 g
4.2 Terminal
rating
Inputs
Mains voltage: Input current depending on the operating state of the unit
Under voltage
U
Mains
120 V
U
Mains
230 V
Safety shutdown from the operating
position takes place should mains
voltage drop
≤
AC 75 V
≤
AC 165 V
Restart is initiated when mains
voltage exceeds
≥
AC 100 V
≥
AC 195 V
State inputs, temperature controller, temperature switch, load controller, pressure
switch, air pressure switch, actuator (except safety loop) of the contact feedback
network (CFN) are used for system supervision and require mains-related input
voltage
Input safety loop
See Terminal rating outputs
Input currents and input voltages
- UeMax
UN +10%
UN +10%
- UeMin
UN -15%
UN -15%
- IeMax
1.5 mA peak
(peak value)
1 mA peak
(peak value)
- IeMin
0.8 mA peak
(peak value)
0.5 mA peak
(peak value)
Contact material recommended for
external signal sources (air pressure
switch, pressure switch-min,
pressure switch-max, etc.)
Gold-plated silver contacts
Transition/settling
behavior/bounce
- Perm. bounce time of contacts
when switching ON/OFF
Max. 50 ms
(after the bounce time, the contact must
stay closed or open)
UN
AC 120 V
AC 230 V
Voltage
detection
- ON
>AC 60 V
>AC 120 V
- OFF
<AC 40 V
<AC 80 V
Analog input X65
DC 0...10 V/DC 0/4...20 mA/0...135
Ω