25 Operation via internal LED
29.11.2011
25.4.5
Display of preset output
Note:
Display is possible only when …
in operating mode or standby,
program sequence for modulating operation via analog preset output.
A
LC
D
B
ild
1
3
/090
8
Press
A
for display of the relative current position of the
actuator.
Signal lamp blinks green.
Display shows
.oP
.
Press
A
(1…3 seconds) for display of the relative current
position.
Signal lamp blinks green.
The
relative
value
.57
of the current position is displayed.
PME7... with actuator
control:
Position of actuator 0°
0
value of potentiometer =
0% display
Position of actuator high-fire
>0°
<90° = value of
potentiometer
<1000
= 100% display
>0
<1000
PME7... with PWM fan:
Current speed
0 rpm = 0% display
Current speed corresponds
to the rated load speed =
100% display
A
1...3 s
Example: Value
.57
A
>3 s
When pressing
+
for >3 seconds, the point after the
number begins to blink.
When the button is released, the value is displayed for 2
minutes.
Signal lamp blinks green.
Then, the normal display appears.
Display: Value
57
, point
.
blinks.