33/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
4 Technical data
29.11.2011
4.7 Signal cable AGV50...
4.7.1 AZL2...
BCI
Signal cable
Color white
Unshielded
Conductor 4 x 0.141 mm²
With jack RJ11
Cable length
- AGV50.100
1 m
Supplier (alternative)
Recommendation:
Hütter
http://www.hkt-
netzwerktechnik.at/index.htm
Location
Under the burner hood (arrangements for
SK
II
EN60730-1 additionally required)
4.8 Dummy plug for RJ11
Dummy plug
For 6 pin modular plug (RJ11)
Supplier Recommendation:
Molex
Order no.: 085 999 3256
4.9 Environmental
conditions
Storage
DIN EN 60721-3-1
Climatic conditions
Class 1K3
Mechanical conditions
Class 1M2
Temperature range
-40...+70 °C
Humidity <95%
r.h.
Transport
DIN EN 60721-3-2
Climatic conditions
Class 2K3
Mechanical conditions
Class 2M2
Temperature range
-40...+70 °C
Humidity <95%
r.h.
Operation
DIN EN 60721-3-3
Climatic conditions
Class 3K3
Mechanical conditions
Class 3M2
Temperature range
-40...+60 °C
Humidity <95%
r.h.
Warning!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, there is a risk of impairment of safety functions and of
electric shock hazard.