73/245
Building Technologies Division
Basic Documentation LME7...
CC1P7105en
Infrastructure & Cities Sector
12 PME71.901...
29.11.2011
Parameter
Parameter
Edit
Value range
Resolution
Factory setting
Password level
Password level
number
Min.
Max.
reading from level
writing from level
600
Power setting
644
Number of pulses per revolution
Edit
2
5
1
3
SO
OEM
646
Settling time for assessment of speed
Edit
1.029 s
2.058 s
0.147 s
2,058 s
SO
OEM
650.00
Speed tolerance band: Speed shutdown
Edit
1% 5% 1%
1%
SO
OEM
650.01
Speed tolerance band: Quick speed shutdown
Edit
1% 10% 1%
3%
SO
OEM
654
Analog input (feedback potentiometer ASZxx.3x required)
0 = 3-position step input
1 = 0...10 V
2 = 0...135
3 = 0...20 mA
4 = 4...20 mA with lockout at
I
<4 mA
5 = 4...20 mA
Edit 0
5
1
1
SO
SO
658.00
PWM values fan: Start PWM
Edit
1% 100%
1%
25% SO
OEM
658.01
PWM values fan: Min. PWM operating range
Edit
0% 20% 1%
0%
SO
OEM
658.02
PWM values fan: Max. PWM operating range
Edit
80% 100% 1%
100% SO
OEM
659.00
Ramp time of fan: Min. low-fire to high-fire
Read only
0 s
74.970 s
0.294 s
2,058 s
SO
---
659.01
Ramp time of fan: Max. low-fire to high-fire
Read only
0 s
74,.70 s
0.294 s
74,970 s
SO
---
659.02
Ramp time of fan: Min. high-fire to low-fire
Read only
0 s
74.970 s
0.294 s
2,058 s
SO
---
659.03
Ramp time of fan: Max. high-fire to low-fire
Read only
0 s
74.970 s
0.294 s
74,970 s
SO
---
660
Tolerance time speed deviation
Read only
0 s
37.85 s
0.147 s
4,998 s
SO
---
674
Neutral band (permitted control offset)
Edit
0 rpm
255 rpm
1 rpm
40 rpm
SO
OEM
675.00
PWM: Min. PWM with prepurging, SEC
Edit
0% 100%
1%
86% SO
OEM
675.01
PWM: Max. PWM with ignition load, SEC
Edit
0% 100%
1%
34% SO
OEM
676
Gain factor speed control
Read only
0 255
1
112 SO
---
677
Integral action time speed control
Read only
0 s
37.485 s
0.147 s
0,441 s
SO
---
678
Derivative action time speed control
Read only
0 s
37.485 s
0.147 s
0 s
SO
---
679.00
Time constant PT1 speed control: Lower speed range high-fire to low-
fire
Edit
0 s
37.485 s
0.147 s
6,027 s
SO
OEM
679.01
Time constant PT1 speed control: Medium speed range high-fire to
low-fire
Edit
0 s
37.485 s
0.147 s
6,027 s
SO
OEM
679.02
Time constant PT1 speed control: Upper speed range high-fire to low-
fire
Edit
0 s
37.485 s
0.147 s
6,027 s
SO
OEM
679.03
Time constant PT1 speed control: Total speed range low-fire to high-
fire
Edit
0 s
37.485 s
0.147 s
6,027 s
SO
OEM
680.00
Speed range for PT1 time constant: Threshold upper speed range
Edit
800 rpm
9000 rpm
10 rpm
4000 rpm
SO
OEM
680.01
Speed range for PT1 time constant: Threshold lower speed range
Edit
800 rpm
9000 rpm
10 rpm
2000 rpm
SO
OEM