Appendix
A.5 Setup Procedure for Wet-Flow Calibration
FUS1010 IP65 NEMA 4X & IP66 NEMA 7
216
Operating Instructions, 01/2013, A5E02951520-AC
The table may contain up to 32 pairs of these slope correction factors. Note that the Kc
factor, unlike these slope correction factors, is entered as a signed percent change in rate,
while these factors are simply rate multipliers. As points are entered, the point editor will
provide list access to the already entered points plus access to the [New Point] menu cell,
used to add a new point. The table may be created in its entirety and then activated by
selecting [Yes] in the [Table Active] menu cell. The entire table may be cleared by selecting
[Yes] in the [Clear Table] menu cell.
Note
Careless use of the calibration tables can have a detrimental impact on the measurement
performance of the flow meter.
Note
Take precautions before enabling these calibration tables. Although it is unlikely that all three
tables would ever be employed in a real installation, three tables are offered for maximum
user flexibility. Since the tables can be disabled without being destroyed, 2 or 3 optimization
strategies may be tested by this means in order to determine which approach is most
effective.
A.5
Setup Procedure for Wet-Flow Calibration
Calibrated SITRANS F 1010 Portable and NEMA Flow Meter Systems
NOTICE
Data Corruption
DO NOT use the field manual installation procedure to start up a wet-flow calibrated
system. Doing so could void the calibration by corrupting essential data.
These are the only authorized instructions to be used when commissioning a wet-flow
calibrated 1010 system.
When a SITRANS F 1010 system is wet-flow calibrated, the flow display computer stores the
installation parameters in its storage memory. Each flow calibration is assigned a unique site
name. Usually, the site name corresponds to the pipe size. For example, a 3-inch carbon
steel, schedule 40 pipe would be given the name "3CS40."
Summary of Contents for FUS1010
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 251: ......
Page 252: ......
Page 253: ......
Page 254: ......
Page 255: ......
Page 256: ......
Page 257: ......
Page 258: ......
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ......
Page 263: ......
Page 264: ......
Page 265: ...21614 C 1011NFPS 7 ...
Page 266: ...1011NFPS 7 C 21614 ...
Page 267: ...1011NFPS 7 C 21614 ...
Page 268: ...21614 C 1011NFPS 7 ...
Page 269: ......
Page 270: ......
Page 271: ......
Page 272: ......
Page 273: ......
Page 274: ...21614 C ...
Page 275: ......
Page 276: ......
Page 277: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 278: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 279: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 280: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 281: ......
Page 282: ......
Page 283: ......
Page 284: ......
Page 285: ......
Page 293: ...Glossary FUS1010 IP65 NEMA 4X IP66 NEMA 7 228 Operating Instructions 01 2013 A5E02951520 AC ...
Page 297: ...Index FUS1010 IP65 NEMA 4X IP66 NEMA 7 232 Operating Instructions 01 2013 A5E02951520 AC ...