E3M080 Line module ”Collective”
32
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
9
E3M080 Line module ”Collective”
9.1 Overview
Line module for
collective detectors
(digital comparator)
I-Bus module with common line processor for all
8 lines
2 line types available (programmable via SWE700A)
Line termination depending on programmable line type
Short circuit can be evaluated as fault or alarm per module (Programming switch
‘S4’)
Line inputs protected against over voltage
Card format 100mm x 200mm
I-Bus address is set at programming switch ’S3’
E3M080
Terminal block X20 (20 terminals)
- mounted on module chassis
- for the connection of the prefabricated cable to
connection level, or
- for direct connection of the periphery
Card chassis
- mounted on module chassis
9.2 Key
data
Line type
Type 1
Type 11
Connectable detector series
See chapter 0 ’Compatibility’
Number of detectors per line
max. 25
Number of wires
2
Twisted cable
recommended
Line resistance
max. 250
Ω
max.
150
Ω
Line capacitance
max. 4
µ
F
Line termination element
EOL22 (Ex)
Transzorb 20V
Line voltage
See chapter 9.3 “Line voltage”
Alarm current limit
45 - 60mA during AI pulse
max. 4,5mA during AI ”dark” phase
Line voltage limit
26,5 ... 27,7V
Quiescent line current
max. 4,5mA
Reset time
3 sec.
Turn-on alarm delay
4.6 sec.
Fault delay
15 sec.
Module quiescent current at 24V
85mA