E3G060 Control module ”Monitored”
69
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
17.6 Programming switches ”S7” & ”S8”
To set horn mode:
Programming switches
Function
S7 S8
Constant horn output (factory setting)
const. horn
int. osci
Intermitted horn output for all horns with internal oscillator (1sec. on /
1sec. off)
Horns driven by other E3G060 cards can be synchronized, by through
contacting K2 plug contacts
int. horn
int. osci
External oscillator input to drive all horns in intermitted mode with
external oscillator
int. horn
ext. osci
Not used
const. horn
ext. osci
Notes:
Switch ”S7” defines global horn mode for all horn outputs. Invert this mode (constant / intermitted)
individually for each horn output by connecting common (X1-1) with corresponding control input
(X1-15.. 20).