Ground fault monitoring (FM compliance)
21
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
6
Ground fault monitoring (FM compliance)
F M
APPROVED
Customer sites covered by the American Factory Mutual (FM) insurance company
have special requirements to their fire panels. The basic FM requirement is to safely
monitor and detect ground faults, of all lines leaving the panel.
The FC700A has been technically adjusted to fulfil those requirements.
For FM installations, adhere the FM Approval mark to the control unit housing next to
the type label.
All modules are delivered pre-set with today’s functionality, so that when setting up
FM installations only, minor adjustments are necessary on some of the modules ac-
cording to the following description.
6.1
Modules overview for FM compliant installations
Modules with part numbers are suitable for FM installations.
Module
Part number
Jumper setting
B3Q700 Control
console
A5Q00004759
yes
E3G070 Control
module
”universal” 546661
yes
E3I040 I-Bus/LON
module
499310
yes
K3I110 LON-I/O
p.c.b.
528854
yes
E3L020 Control
module
”I/O”
546645
no
E3G060 Control
module
”monitored” 542539
no
E3H020 C-Bus
Gateway
546658
no
Remarks
–
With an E3L030 board installed, the system is not FM compliant.
–
Please verify part of used modules and check jumper settings as described in the following scheme.