E3M111 Line module ”SynoLOOP”
38
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
10.4 Important
components
Fuses
F1 7 1A/T* Module supply 24V
F1 8 1A/T* Module supply 5V
* Fuse with high breaking capacity
(sand-filled)
Fuses
F1...F16 1A/F Lines 1..4
SMD fuses (can only be changed at factory)
Plug-in terminals "K1":
Supply to "I-Bus" modules
Flat cable header "ST1" (26-pin):
I-Bus
Programming switch "S3":
"I-Bus address" setting
(see chapter Programming switch)
Connector 'ST10':
unused
Fuses
F19/F20 1A/F
Supply voltage for DC modules
SMD fuses (can only be
changed at factory)
Service LED "H1":
pulsating = Communication with detection line(s) ok
continuous = Module probably defective
not active = no line connected, or not programmed
E3M111
F1
F16
F20
F19
H1
S3
ST1
ST10
F18
F17
K1
ON
1
1
4
µ
P
ASIC
I-Bus
10.5 Programming
switch
”S3”
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch ”S3”. Maximum 16
I-Bus devices.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number
1
on
off off off off off
2
2
off
on
off off off off
3
3
on
on
off off off off
4
4
off off
on
off off off
5
5
on
off
on
off off off
6
6
off
on
on
off off off
7
7
on
on
on
off off off
8
8
off off off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3-1...6” are set to ”off” at the factory