E3L030 Control module VdS
62
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
15.5 Programming
switch
”S3”
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch ”S3”. Maximum 16
I-Bus devices.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0
Module out of commission (unused) 1)
off
off
off
off
off
off
1
I-Bus user number 1
on
off off off off off
2
2
off
on
off off off off
3
3
on
on
off off off off
4
4
off off
on
off off off
5
5
on
off
on
off off off
6
6
off
on
on
off off off
7
7
on
on
on
off off off
8
8
off off off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3-1...6” is set to ”off” at the factory
1) E3L030 functions in ”emergency operation” with I-Bus address 0
15.6 Special
functions
Emergency operation
An alarm which occurs during system malfunction (emergency operation) can still
be handled via FBF and ÜE and FSD can also still be activated.
Function overview during ”emergency operation”
Function Emergency
operation E3L030
Emergency
operation CPU
FBF
Indicator ”ÜE activated”
●
●
Indicator ”LEDs 5, 6, 7, T5 operational”
-
●
Function ”Silence audible signal”
●
●
ÜE
Function ”Activate ÜE”
●
●
FSD
Function ”Activate FSD unlocking”
●
●
SST
(Extinguishing standard interface)
-
-
TK
(Door switch control unit)
-
●