E3M080 Line module ”Collective”
33
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
9.3 Line
voltage
'Alarm'
3,2 ... 16,4V
23,3 - 27,7V
0 - 3,7V
17,3-24,1V
0
[V]
Line type 1
0
[V]
Line type 11
'Alarm'
3,2 ... 16,4V
'open line'
21,4 - 27,7V
'Short circuit'
0 - 3,7V
'Leak'
15,7 - 19,7V
15,7 - 18,0V
'Quiescent'
18,9-22,2V
'Quiescent'
'open line'
'Leak'
'Short circuit'
Overlapping
The different line voltage ranges are overlapping (tolerances).
However, there is only
ath the time possible
(visible at the control unit)
one state
9.4
Line termination element (Application see chapter 9.2)
Transzorb
(Part number 460 051)
EOL22 (Ex)
(Part number 516 222)
9.5
Compatibility (detector <–> line type)
Line type 11
Line termination with
transzorb 20V
Synova
TM
detectors:
OP620C, HI62xC, DM110x, DC1192
Ex detectors (without restrictions)
used via DC1192 with SB3: DO1101-Ex, DT110x-Ex
Line type 1
Line termination with
EOL22 (Ex)
Special detectors:
DLO1191, (with mixed lines also OP620C, HI62xC, DM110x, DC1192)