E3G070 Control module ”Universal”
72
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
18.3 Important
components
H1
H8
X60
X12
Y12
Y13
F6
F7
F8
F9
S2
ST1
S3
F4
F3
F2
K2
F5
X13
F1
ON
1
ON
K1
1
4
0 -Resistors
Ω
"Y12" = Remote transmission alarm as make contact (factory setting)
"X12" = Remote transmission alarm as break contact
"Y13" = Remote transmission fault as break contact (factory setting)
"X13" = Remote transmission fault as make contact
Fuse
F1 5A/T Module supply
Fuses
F2, F3 0,63A/T Supply output
F4, F5 0,25A/T Control outputs / inputs
F6...F9 2A/T* Control lines for alarm devices
* Fuse with high breaking capacity (sand-filled)
Flat cable header "ST1" (26-pin): I-Bus
Plug-in terminals "K1":
Supply for "I-Bus" modules
Maintenance switch"S2":
To switch on maintenance LEDs for test
purposes. In addition to driver output,
enables the corresponding LED (H1...H11)
to be activated.
= LED (H1..H11) lights if output
is activated.
S2-on
Programming switch "S3":
"I-Bus address" setting (see below)
Connector "K2"
unused
Test LEDs H1...H11 at rear.
Allocation of the individual LEDs
see chapter Connections
Jumper "X60":
Ground fault monitoring 'control unit
''out' = inactive (factory setting)
'in' = active
(for application details see chapter
Ground fault monitoring)
E3G070
ASIC
I-Bus
18.4 Programming
switch
”S3”
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch ”S3”. Maximum 16
I-Bus devices.
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number
1
on
off off off off off
2
2
off
on
off off off off
3
3
on
on
off off off off
4
4
off off
on
off off off
5
5
on
off
on
off off off
6
6
off
on
on
off off off
7
7
on
on
on
off off off
8
8
off off off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3-1...6” are set to ”off” at the factory
The I-Bus address setting is given as default by the tool (SWE700A) as address 15, therefore the
programming switch 'S3' of the E3G070 must be set accordingly.