E3M080 Line module ”Collective”
34
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
9.6 Important
components
Programming switch "S4":
Allows the line short circuit to be evaluated
either as fault or alarm
(common to all 8 lines).
on = Short circuit evaluated as alarm
(AI pulse generator activ)
off = Short circuit evaluated as fault
= no function
set to "off" at the factory
S4-2
S4-1
S4-2
Sicherungen
F1 / F2 1A/F Line 1
F3 / F4 1A/F Line 2
F5 / F6 1A/F Line 3
F7 / F8 1A/F Line 4
F9 / F10 1A/F Line 5
F11 / F12 1A/F Line 6
F13 / F14 1A/F Line 7
F15 / F16 1A/F Line 8
SMD fuses
(can only be
changed at factory)
Fuse
F17 1A/F Module supply
SMD fuse
(can only be changed at factory)
Flat cable header "ST1" (26-pin):
I-Bus
Plug-in terminals "K1":
Supply to "I-Bus" modules
Connector "ST10":
unused
Programming switch "S3": "I-Bus address" setting
(see chapter programming switch)
E3M080
F16
F1
S4
ST10
ST1
S3
K1
1
4
1
1
ON
ON
ASIC
I-Bus
µ
P
9.7 Programming
switch
”S3”
To set I-Bus address. Each element (module) connected to the I-Bus must have an
individual address (number). This is set on programming switch ”S3”. Maximum 16
I-Bus devices.
Function / I-Bus address
Programming switch S3
Nr.
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number
1
on
off off off off off
2
2
off
on
off off off off
3
3
on
on
off off off off
4
4
off off
on
off off off
5
5
on
off
on
off off off
6
6
off
on
on
off off off
7
7
on
on
on
off off off
8
8
off off off
on
off off
9
9
on
off off
on
off off
10
10
off
on
off
on
off off
11
11
on
on
off
on
off off
12
12
off off
on
on
off off
13
13
on
off
on
on
off off
14
14
off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3-1...6” are set to ”off” at the factory