background image

Features 

 

Individually addressed and controlled 
multi-candela S/V (speaker/visible) notification 
appliances provide: 

 

Multi-candela xenon strobe with synchronized 1 Hz 
flash rate and with intensity 

programmable from the 

control panel

 or jumper selected as 15, 30, 75, or 

110 cd 

 

Advanced addressable notification controlled by 

IDNAC 

SLCs

 from Simplex

®

 4100ES fire alarm control panels 

with EPS/EPS+ power supplies (and 4009 IDNAC 
Repeaters) providing 

regulated 29 VRMS

 allowing 

strobes to operate with lower current even under battery 
backup 

 

Wiring supervision to each strobe allowing “T-tapped” 
connections for Class B circuits to simplify wiring 
(Class A circuits require in/out wiring) 

 

TrueAlert Device Reports

 at the control panel detailing 

appliance point ID, custom label, type, and candela 
setting (see sample on page 2) 

 

Magnet test diagnostics

 to assist checkout and testing of 

appliances and wiring 

 

Compatibility with ADA requirements; (refer to 
important installation information on page 3) 

 

Compatibility with legacy TrueAlert addressable 
systems for upgrade and replacement (see page 4) 

 

Strobe operation is listed to UL 1971 and ULC-S526* 

LED indicator and magnet test feature: 

 

Appliance LED can be selected to display each polling 
cycle to indicate appliance supervision 

 

In diagnostic mode, the magnet test pulses the LED to 
indicate appliance address 

AND pulses to indicate the 

intensity selection

; a brief output of the strobe is also 

selectable to confirm operation 

Mechanical design features:  

 

Rugged, high impact, flame retardant thermoplastic 
housings are available for wall or ceiling mount 

 

Wall mount housings are available in red or white 

 

Wall mount options include electrical box adapters, 
separate covers to convert color, and red wire guards 

 

Ceiling mount housing is white 

Audible notification appliance (speaker): 

 

High quality voice and tone reproduction with taps for 
¼, ½, 1, or 2 W, at 25 or 70.7 VRMS 

 

Speakers have capacitor input for connection to DC 
supervised NACs and are wired separately from strobes 

 

Listed to UL 1480 and ULC S541* 

 

Compliant with NFPA 72, 520 Hz Low Frequency 
Signal Requirements for Sleeping Areas 

*

   See page 2 for additional listing details and wire guard listings. This product has been 

approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the 

California Health and Safety Code. See CSFM Listing 7320-0026:322 for allowable values 

and/or conditions concerning material presented in this document.

 

Accepted for use – City 

of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; 

contact your local Simplex product supplier for the latest status. Listings and approvals 

under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.  

 

 

Wall and Ceiling Mount S/Vs with Addressable Strobes 

Description 

 

Multi-Candela TrueAlert S/Vs with speaker and 
addressable strobe

 provide convenient installation to 

standard electrical boxes with extensions. The strobe is 
individually addressed and individually controlled with 
power, supervision, and control supplied from a Simplex 
fire alarm control panel providing 

IDNAC

 Signaling Line 

Circuits (SLCs). (See compatibility list on page 4.) 
Speakers are wired separately. 

Strobe Application Reference 

 

Proper selection of visible notification is dependent on 
occupancy, location, local codes, and proper applications 
of: the 

National Fire Alarm and Signaling Code

 

(NFPA 72), ANSI A117.1; the appropriate model 
building code: BOCA, ICBO, or SBCCI; and the 
application guidelines of the Americans with Disabilities 
Act (ADA). 

IDNAC SLC Operation Advantage 

 

TrueAlert S/V Appliances with Addressable 
Strobes on IDNAC SLCs

 provide visible notification 

using a single two-wire circuit that also 

confirms 

connection to the individual notification appliance’s 
electronic circuit

. This operation increases circuit 

supervision integrity by providing supervision that 
extends beyond the appliance wiring connections. 

 

TrueAlert Addressable Notification Appliances 

UL, ULC, CSFM Listed; FM Approved;

 

 Multi-Candela Speaker/Visible 

 

MEA (NYC) Acceptance*

 (S/V) 

Appliances

 

 

 

S4906-0006-7  5/2014

 

 