Page EN-6
XCT-8 Sanitary Transducer– INSTRUCTION MANUAL
7ML19985HX61
English
Mounting
Mount the transducer so that it is above the maximum material level by more than the
blanking value to ensure that accurate results are achieved. Refer to the associated
transceiver manual for information on setting the blanking value.
The transducer must be mounted so that the axis of transmission is perpendicular to the
measured surface to get the most reliable signal. See
Transducer Placement
for an example.
Always use an isolation gasket
(customer supplied) when
mounting the XCT-8. This gasket
reduces ultrasonic energy
coupling to the mounting
hardware.
Transducer must be mounted on a
4” ferrule. Do not mount by conduit
threads.
After applying the sanitary clamp,
adjust the clamp as required to
seal the transducer to the vessel
ferrule.
Do not over tighten the
mounting.
Hand tightening of the
mounting hardware is sufficient.
•
Sanitary Clamp
– Siemens
Milltronics 7ML1830-1BR
May be substituted with a
clamp meeting these
specifications:
•
4” single hinge, sanitary clamp
•
4.820” interior diameter
•
300 psi rated
•
3A compliant ferrule
– customer supplied to 3A specification
Refer to the associated transceiver manual for details on blanking, standpipe length, and
wiring.
XCT - 8 transducer
isolating gasket
(customer
supplied)
sanitary clamp
3A compliant ferrule
Summary of Contents for Echomax XCT-8
Page 1: ...Instruction Manual November 2004 SANITARY xct 8 English Deutsch Español Français ...
Page 2: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 12: ...Page EN 10 XCT 8 Sanitary Transducer INSTRUCTION MANUAL 7ML19985HX61 English ...
Page 22: ...Seite DE 10 XCT 8 Sanitärsensor BETRIEBSANLEITUNG 7ML19985HX61 Deutsch ...
Page 32: ...Página ES 10 Sensor sanitario XCT 8 MANUAL DE OPERACIÓN 7ML19985HX61 Español ...
Page 42: ...Page FR 10 Transducteur sanitaire XCT 8 MANUEL D UTILISATION 7ML19985HX61 Français ...