ENGLISH
18
610.43 410.21
Siemens AG
4.3
Cooling
Self-cooling
The motors are designed for self-cooling.
The rated data only apply if the ambient temperature does not exceed 40 °C (104 °F) as a
result of the installation conditions.
Recommendation:
Maintain a gap of 100 mm to adjacent components on at least three sides in order to allow
waste heat to dissipate.
Forced ventilation
Degree of protection
IP 54
(EN 60529)
Fan connector
1FT6 08., 1FT6 10.
Power connector, size 1
Pin assignment according to Fig. 7
Direction of air flow
1FT6 08., 1FT6 10.
from the non-drive to the drive end
Only connect the ventilation unit via a suitable motor contactor (not included in the
scope of delivery).
Connection values
1FT6 08., 1FT6 10.
1 AC 230/260 V, 50/60 Hz, 0.3 A
The ventilation unit can, in principle, be retrofitted. This is performed exclusively by
SIEMENS Service.
Note: changed plug size/winding.
Do not take heated outgoing air in again to cool the motor.
Minimum clearances of the air exhaust outlet from customized components:
Water-cooling
Closed coolant circuit with heat exchange unit required. Water cooling cannot be retrofitted.
If the cooling circuit has been filled and frost can be expected, a commercially available
antifreeze agent must be added. Please refer to the manufacturer's documentation for
usage and dosage (max. 50 %). Do not mix different types of antifreeze.
Do not use any nonferrous metals (e.g. copper or brass pipework) in the cooling circuit
(electrolyte formation).
Degree of protection
IP 64-68
(EN 60529)
Cooling water connection
1FT6 06. - 1FT6 10.
G3/8"
Cooling water flow
1FT6 06. - 1FT6 10.
(5 ±0.75) l/min
Pressure
1FT6 06. - 1FT6 10.
max. 2.5 bar
Motor type
Minimum distance (mm)
1FT6 08
20
1FT6 10
30