FORM 7: SYSTEM DATA
e
SIZE
250
300
400
500
600
800
1000
1) AC/AC Efficiency
- 100% nominal load
%
91,80
92,00
93
93,5
94,1
94,5
94,5
- 75% nominal load
%
91,81
92,01
93,5
94,1
94,8
94,8
94,8
- 50% nominal load
%
92,40
92,60
93
93,6
94,3
94,4
94,4
- 25% nominal load
%
89,00
89,20
90
90,3
91
91,2
91,2
2) Maximum Heat dissipation @ Full Load
kW
17,9
20,9
24,1
27,8
30,1
37,2
46,6
3) Noise @ 1 metre as per ISO3746
dBA
70
70
70
78
78
78
78
4) Air Flow
m
3
/h
3200
3200
10000
10000
10000
10000
10000
5) Operating Temperature
°C
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
6) Storage Temperature
°C
-20 / 70
-20 / 70
-20 / 70
-20 / 70
-20 / 70
-20 / 70
-20 / 70
7) Maximum relative humidity (non
condensing):
(@ 40°C)
%
60
60
60
60
60
60
60
(@ 25°C)
%
90
90
90
90
90
90
90
8) Elevation without derating
m
1000
1000
1000
1000
1000
1000
1000
9) Power derating over 1000m each
1000m
%
5
7c: 250/1000kVA- 12Pulse
IV306E - SP133E
Siel S.p.A.