![Siel Safepower Evo 100 Manual Download Page 42](http://html1.mh-extra.com/html/siel/safepower-evo-100/safepower-evo-100_manual_1265224042.webp)
e
Size
kVA
100
120
160
200
1) Nominal input votage 3Ph
(Note 1)
Vca
400
400
400
400
2a) Tolerance on voltage (Float
charge):
- Pb Battery
%
-13 +15
-13 +15
-13 +15
-13 +15
- Sealed Pb Battery
%
-13 +15
-13 +15
-13 +15
-13 +15
2b) Tolerance on voltage (Without
battery discharge) :
%
-20
-20
-20
-20
3) Nominal frequency (Note 2)
Hz
50
50
50
50
4) Frequency range
Hz
45÷65
45÷65
45÷65
45÷65
5) Nominal input power @ Battery on
float, without PFC
kVA
106
125
167
208
6) Medium power factor @ 400,
nominal load (Note 3)
cos ø
0,9
0,9
0,9
0,9
7) Max input power @ Battery on
recharge, without PFC
kVA
134
154
209
251
8) Max input current @ 400V,
without PFC, battery on recharge
Aac
194
223
302
363
9a) Time before Start-Up (Option:
selectable)
s
0,10, 20
0,10, 20
0,10, 20
0,10, 20
9b) Start-Up time
s
10-30
10-30
10-30
10-30
10) Efficiency
%
96,8
98,1
98,1
98,3
11) THD
%
28
28
28
28
Note 1: 380Vac - 415Vac: Option
Note 2: 60Hz: Option
Note 3: PFC option (otherwise 0,83)