e
Size
kVA
20
30
40
50
60
80
1) Nominal input votage 3Ph
(Note 1)
Vca
400
400
400
400
400
400
2a) Tolerance on voltage (Float
charge):
- Pb Battery
%
-13 +15
-13 +15
-13 +15
-13 +15
-13 +15
-13 +15
- Sealed Pb Battery
%
-13 +15
-13 +15
-13 +15
-13 +15
-13 +15
-13 +15
2b) Tolerance on voltage (Without
battery discharge) :
%
-20
-20
-20
-20
-20
-20
3) Nominal frequency (Note 2)
Hz
50
50
50
50
50
50
4) Frequency range
Hz
45÷65
45÷65
45÷65
45÷65
45÷65
45÷65
5) Nominal input power @ Battery on
float, without PFC
kVA
22
33
44
54
65
86
6) Medium power factor @ 400,
nominal load (Note 3)
cos ø
0,9
0,9
0,9
0,9
0,9
0,9
7) Max input power @ Battery on
recharge, without PFC
kVA
30
41
58
68
79
107
8) Max input current @ 400V,
without PFC, battery on recharge
Aac
44
60
84
99
115
155
9a) Time before Start-Up (Option:
selectable)
s
0,10, 20
0,10, 20
0,10, 20
0,10, 20
0,10, 20
0,10, 20
9b) Start-Up time
s
10-30
10-30
10-30
10-30
10-30
10-30
10) Efficiency
%
94,4
94,6
94,6
95,5
95,6
95,6
11) THD (Note 4)
%
7
7
7
7
7
7
2b: RECTIFIER INPUT TECHNICAL DATA 20-80kVA 12-PULSE
Note 1: 380Vac - 415Vac: Option
Note 2: 60Hz: Option
Note 3: PFC option (otherwise 0,83)
Note 4: Option (otherwise 9%)
FORM 2: RECTIFIER INPUT TECHNICAL DATA
IV306E - SP133E
Siel S.p.A.