FORM 6: STATIC SWITCH TECHNICAL DATA
e
SIZE
20
30
40
50
60
80
1) Nominal Power
kVA
20
30
40
50
60
80
2) Input/Output Voltage (Note1)
V
400
400
400
400
400
400
3) Acceptance range of Mains Voltage
(low and high theresold are adjustable
between 3% and 50%)
%
+10/-10
+10/-10
+10/-10
+10/-10
+10/-10
+10/-10
4) Input/Output frequency (Note1)
Hz
50
50
50
50
50
50
5) Power Overload:
- 30'
%I
N
150
150
150
150
150
150
- 90s
%I
N
300
300
300
300
300
300
- 5s
%I
N
500
500
500
500
500
500
- 2s
%I
N
680
680
680
680
680
680
- 1s
%I
N
700
700
700
700
700
700
- 500ms
%I
N
800
800
800
800
800
800
- 200ms
%I
N
900
900
900
900
900
900
- 100ms
%I
N
1000
1000
1000
1000
1000
1000
- 50ms
%I
N
1100
1100
1100
1100
1100
1100
- 20ms
%I
N
1200
1200
1200
1200
1200
1200
- 10ms
%I
N
1400
1400
1400
1400
1400
1400
- 3ms
%I
N
1500
1500
1500
1500
1500
1500
6) Transfer time:
- FROM INVERTER TO RESERVE
a) inverter fault
ms
0,9
0,9
0,9
0,9
0,9
0,9
b) inverter overload or manual control
ms
0
0
0
0
0
0
- FROM RESERVE TO INVERTER
ms
0
0
0
0
0
0
7) Efficiency @ full load
%
99,2
99,2
99,2
99,2
99,2
99,2
Note 1: On demand 380Vac, 415Vac, 60Hz
6a: Static Switch 20/80kVA
IV306E - SP133E
Siel S.p.A.
Form 6 - Page 1 of 3