![Siel Safepower Evo 100 Manual Download Page 46](http://html1.mh-extra.com/html/siel/safepower-evo-100/safepower-evo-100_manual_1265224046.webp)
e
SIZE
kVA
100
120
160
200
1a) Output Voltage (Stationary
Battery)
- Float
Vcc
436
436
436
436
- Boost
Vcc
475
475
475
475
1b) Output Voltage (Sealed
Battery)
- Float
Vcc
446
446
446
446
1c) Output Voltage (Without
Battery discharge)
Vcc
396
396
396
396
2) DC Voltage Range
Vcc
330-500
330-500
330-500
330-500
3) Voltage regulation in steady
state condition for 100% load
variation and/or input voltage
%
±1
±1
±1
±1
4) Voltage ripple (Vrms/Vb x
100)
%
<1
<1
<1
<1
5) Nominal current
Acc
200
240
320
399
6) Max output rectifier current
Acc
240
280
380
459
7a) Max battery charging current
@ inverter full load
Acc
40
40
60
60
7b) Max battery charging current
Acc
216
252
342
414
8) Battery charging current
range:
- min
Acc
5
5
5
5
- max
Acc
216
252
342
414
9) Battery charging method
10) Maximun time to recharge
battery
SIZE
kVA
100
120
160
200
1) Recommended N° of Pb cells
N°
198
198
198
198
2) Nominal voltage
Vcc
396
396
396
396
3) Float voltage
Vcc
446
446
446
446
4) N° of Ni-Cd cells
N°
5) End of descharge voltage (Pb
Battery)
Vcc
330
330
330
330
6) End of descharge current
Acc
257
308
410
513
360,720,1440, 2880 min.
Contact SIEL
BATTERY
FORM 3: RECTIFIER OUTPUT AND BATTERY TECHNICAL DATA
3b: RECTIFIER OUTPUT: 100-200kVA
DIN41773
IV306E - SP133E
SIEL S.p.A.
Form 3 - Page 2 of 3