FORM 4: INVERTER INPUT TECHNICAL DATA
SIZE
kVA
20
30
40
50
60
80
1) Nominal voltage
Vcc
446
446
446
446
446
446
2) DC Voltage range
Vcc
330÷500
330÷500
330÷500
330÷500
330÷500
330÷500
3) Pre-alarm end
discharge voltage
Vcc
350
350
350
350
350
350
4) DC current at nominal
voltage
Acc
39
58
77
95
114
152
5) Max DC current at
end discharge voltage
Acc
52
78
103
129
154
206
e
SIZE
kVA
100
120
160
200
1) Nominal voltage
Vcc
446
446
446
446
2) DC Voltage range
Vcc
330÷500
330÷500
330÷500
330÷500
3) Pre-alarm end
discharge voltage
Vcc
350
350
350
350
4) DC current at nominal
voltage
Acc
190
228
304
380
5) Max DC current at
end discharge voltage
Acc
257
308
410
513
e
SIZE
kVA
250
300
400
500
600
800
1000
1) Nominal voltage
Vcc
446
540
540
540
540
540
540
2) DC Voltage range
Vcc
330÷500
400-580
400-580
400-580
400-580
400-580
400-580
3) Pre-alarm end
discharge voltage
Vcc
350
430
430
430
430
430
430
4) DC current at nominal
voltage
Acc
476
471
622
776
925
1228
1535
5) Max DC current at
end discharge voltage
Acc
643
636
841
1048
1250
1660
2075
4a: INVERTER INPUT: 20/100kVA
4b: INVERTER INPUT: 100/200kVA
4c: INVERTER INPUT: 250/1000kVA
IV306E - SP133E
Siel S.p.A.
Form 4 - Page 1 of 1