background image

8

3059

10

2019

-

PJC 221 & 222

Hydraulic System - PHC 024 Setup

EN

MC_0095

PHC 024 (Controller for hydraulic thrusters)

Most functions requires PHC 024 with fi rmware V.1.101 or newer!

Bow/Stern Direction:

Values: Normal (default)/Inverted

Switches between Normal and Inverted running direction for the thruster. Direction need to be inverted if 

incorrect prop rotation.

Pump Control (PTO Mounted Pump)

Values: Auto(default)/Always ON/Not Available

When «Pump Control» is set to «Auto», the system will automatically control load sharing between two PTO 

pumps by deactivating the second PTO pump when not needed (two PTO pumps/control valves required) to 

reduce heat generation in the system and save fuel/energy.

When any thruster is running, both PTO pumps will be active to ensure good performance. When an SPS 

stabilizer system is active, one PTO pump will be deactivated to save power. If stabilizers are active and 

the system pressure drops below 80bar, the system will activate the second PTO pump for 15 minutes 

to increase the fl ow capacity and maintain required pressure. After 15 minutes the second pump will be 

deactivated unless the pressure is still below 80 bar.

“Pump Control” is set to “Not Available” when “Thruster Stern” is set to “with Bypass Valve”. “Pump Control” 

will then not be able to edit.

              

(NB: “Pump Control: Auto” must only be used on PHC 024 with fi rmware V.1.008 or higher)

Cooling Pump 

Values: Always Running/Temp Controlled(default)

When the option “Temp Controlled” is selected, the cooling pump will start when oil temperature exceeds 

50°C/122°F and stop when the oil temperature goes below 40°C/104°F. On systems with two oil tanks, this 

setting will apply to both tanks.

Cooling Signal Output

Values: Normal (default)/Inverted

Set to Normal when using a hydraulic cooling pump. Should be set to Inverted when using an electrical 

cooling pump with a 10 2380A-12/24V relay box

Press the button below 

 to return to the previous menu.

Press the button below 

 to edit the selected parameter.

Parameter value will start to blink, use joystick to alter value. 

Press the button below 

 to save edited parameter to device

Press the button below 

 to cancel editing without saving.

 

Control Panel Setup Buttons 

EN

MC_0115

Setup

Default  in systems 

without stabilizers

Combining Stabilizer with AC & DC Thrusters

EN

MC_0115

Setup

SETUP

NOTICE regarding following Location modes: If the boat has Side-Power stabilizer and AC or DC thrusters the thruster 

location should be set as BOW-STB or STERN-STB. This so the hydraulic controller are shown at the left side in display 

and thruster(s) at the right side of the display.

 

Default  in systems 

without stabilizers

HYD-DC

HYD-AC

HYD-AC-DC

3.0

3.1

3.2

3.3

3.4

Summary of Contents for S-linkControl Panel PJC221

Page 1: ...SLEIPNER MOTOR AS P O Box 519 N 1612 Fredrikstad Norway www side power com Document id Revision Date 3059 10 Control Panels PJC 221 PJC 222 To download your language go to www side power com K e e p t...

Page 2: ...System PDC 101 Setup 10 AC System PDC 201 Setup 10 AC System PDC 301 Setup 11 DC System Automatic Main Switch Setup 12 DC System PPC SR150000 SR61242 Setup 12 DC System RCRS 1 RCRS 2 Setup 13 DC Syste...

Page 3: ...ing to international or special national regulations Instructions in this guide cannot be guaranteed to comply with global electric mechanic regulations classification rules It is the installers respo...

Page 4: ...he direction of the arrows at select ed power Press for more and for less power 6 steps If any control unit are running the thruster in opposite direction to the hold function the hold function will b...

Page 5: ...EN 60533 Weight 215 gr Description Minimum Maximum Units Comment Input voltage 9 31 Volt DC Powered from S Link Current Voltage 20 120 mA External Alarm Buzzer Voltage 31 Volt DC External Alarm Buzzz...

Page 6: ...222 Supply 12V 24V DC S link External alarm buzzer 12V 24V DC max 0 5A Internal fuse relay External alarm buzzer connection Rear side of panel Connections for optional external buzzer audible alarm C...

Page 7: ...s can not be operated to auto setup is completed OR RUN SETUP DEVICES IN CONFLICT Detected devices in con ict Two or more thrusters defined as same instance bow stern bow STB Stern STB Run Setup proce...

Page 8: ...lve Pump Control will then not be able to edit NB Pump Control Auto must only be used on PHC 024 with rmware V 1 008 or higher Cooling Pump Values Always Running Temp Controlled default When the optio...

Page 9: ...o protect the thruster during deceleration and will close while thruster is running By selecting with Bypass Valve you activate this signal and addition change ramp parameters to match this setup All...

Page 10: ...display and thruster s at the right side of the display Direction Values NA Not Available AC System PDC 101 Setup AC System PDC 201 Setup EN EN MC_0096 MC_0096 PDC 201 Location Values BOW STERN BOW ST...

Page 11: ...uster location should be set as BOW STB or STERN STB This so the hydraulic controller are shown at the left side in display and thruster s at the right side of the display Direction Values Normal defa...

Page 12: ...his so the hydraulic controller are shown at the left side in display and thruster s at the right side of the display Direction Values Normal default Inverted Switches between Normal and Inverted runn...

Page 13: ...t sideways when both thrusters are operated simultanously with input from the remote only MSI8730 Location Values BOW STERN BOW STB STERN STB Set the location for selected device Use BOW or STERN in a...

Page 14: ...t of devices found can fill more than one screen A scroll bar indicates the position of the selected item The joystick s operates the thrusters as normal while info is displayed This will be useful fo...

Page 15: ...AN bus error status for the panel Showing no error and signal condition is good Example showing lots of error and very bad signal conditions DIAGNOSTIC DISPLAY Rx Error Count Receive error counter Err...

Page 16: ...CELSIUS Default FAHRENHEIT Set the panel temperature displaying unit WHEN RETRACT IS OUT Values NO WARNING Default WARNING EVERY 10sec Select WARNING EVERY 10sec for external buzzer or lamp warning ev...

Page 17: ...larm De scription pages in the Auto Reset column you can see which alarms that are auto reset SPECIFIC ALARMS STOP BUTTON Pressing the STOP button on a hydraulic panel will activate the dump valve and...

Page 18: ...shown in a dual stern thruster setup Battery indicator will be shown here in a single DC electric stern thruster setup BOW STERN BOW STB STERN STB Examples of display view for di erent panels applica...

Page 19: ...V thrusters Motor temperature indicator From 70 C 158 F to 130 C 266 F Symbol shown when a DC Thruster is used in a dual bow or dual stern setup Proportional Thruster Display Symbols EN MC_0053 Thrust...

Page 20: ...light in display and continous short beeps Voltage below 8 5V 15V 12V 24V system Temperature above 110 o C 230 o F None 4 Red backlight in display and continous short beeps If one or more of the thrus...

Page 21: ...Language English Backlight Level 5 Backlight Night Color Green Backlight Nightlevel 1 Timer Auto O 05 min Hold Calibration 70 Bow and Stern All system devices will be erased from memory Setup procedu...

Page 22: ...r 2 3 Motor relay fault Turn off thruster battery main switch Thruster must be serviced by author ized personel 8 Critical Error 2 3 PPC output fail PPC must be sent for service 9 Low Motor Current 2...

Page 23: ...1 2 3 Any Stabilizer alarm See stabilizer panel for more info 28 AC Motor Overtemp Yes 1 2 3 Hydraulic AC motor power pack over temp Higher than 120 C 248 F Stop running and wait for tempera ture to d...

Page 24: ...20mA sensor short circuit Wires shorted or sensor defective check wiring sensor Replace sensor 10505 0 13 PHC AI 2 Open Circuit Analog Input 2 4 20mA sensor open circuit Sensor not connected or wire b...

Page 25: ...0 55 PHC ECI Cooling Pump Overtemp ECI cooling pump temperature higher than 100 C 212 F Check ECI cooling pump for damages Replace ECI cooling pump 10524 0 100 PHC ECI Cooling Pump No Communication No...

Page 26: ...26 3059 10 2019 PJC 221 222 MC_0037 Notes EN...

Page 27: ...Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure easier Note Type...

Page 28: ...cument was correct at the time it was published However Sleipner Motor AS can not accept liability for any inaccuracies or omissions it may contain Continuous product improvement may change the produc...

Reviews: