PJC 221 & 222
Hydraulic System - PHC 024 Setup
EN
MC_0095
PHC 024 (Controller for hydraulic thrusters)
Most functions requires PHC 024 with fi rmware V.1.101 or newer!
Bow/Stern Direction:
Values: Normal (default)/Inverted
Switches between Normal and Inverted running direction for the thruster. Direction need to be inverted if
incorrect prop rotation.
Pump Control (PTO Mounted Pump)
Values: Auto(default)/Always ON/Not Available
When «Pump Control» is set to «Auto», the system will automatically control load sharing between two PTO
pumps by deactivating the second PTO pump when not needed (two PTO pumps/control valves required) to
reduce heat generation in the system and save fuel/energy.
When any thruster is running, both PTO pumps will be active to ensure good performance. When an SPS
stabilizer system is active, one PTO pump will be deactivated to save power. If stabilizers are active and
the system pressure drops below 80bar, the system will activate the second PTO pump for 15 minutes
to increase the fl ow capacity and maintain required pressure. After 15 minutes the second pump will be
deactivated unless the pressure is still below 80 bar.
“Pump Control” is set to “Not Available” when “Thruster Stern” is set to “with Bypass Valve”. “Pump Control”
will then not be able to edit.
(NB: “Pump Control: Auto” must only be used on PHC 024 with fi rmware V.1.008 or higher)
Cooling Pump
Values: Always Running/Temp Controlled(default)
When the option “Temp Controlled” is selected, the cooling pump will start when oil temperature exceeds
50°C/122°F and stop when the oil temperature goes below 40°C/104°F. On systems with two oil tanks, this
setting will apply to both tanks.
Cooling Signal Output
Values: Normal (default)/Inverted
Set to Normal when using a hydraulic cooling pump. Should be set to Inverted when using an electrical
cooling pump with a 10 2380A-12/24V relay box
Press the button below
to return to the previous menu.
Press the button below
to edit the selected parameter.
Parameter value will start to blink, use joystick to alter value.
Press the button below
to save edited parameter to device
Press the button below
to cancel editing without saving.
Control Panel Setup Buttons
EN
MC_0115
Setup
Default in systems
without stabilizers
Combining Stabilizer with AC & DC Thrusters
EN
MC_0115
Setup
SETUP
NOTICE regarding following Location modes: If the boat has Side-Power stabilizer and AC or DC thrusters the thruster
location should be set as BOW-STB or STERN-STB. This so the hydraulic controller are shown at the left side in display
and thruster(s) at the right side of the display.
Default in systems
without stabilizers
HYD-DC
HYD-AC
HYD-AC-DC