background image

 25

3059

10

2019

-

PJC 221 & 222

                           

PHC-3 Alarm Descriptions

EN

MC_0117

Fault Code

Description

Cause

Action

10500.0.10

PHC Oil Level - Level Low

Hydraulic oil level is low

-Limit the use of thruster

-Inspect hydraulic oil level

-Check system for leaks and refi ll hydraulic oil

10500.0.13

PHC Oil Level - Open Circuit

Analog oil level sensor open circuit

-Sensor not connected or wire break.

-Verify sensor type in parameter 0201

-Disconnect sensor and measure that sensor resistance value is in 

range 0-180ohm.

10501.0.11

PHC Oil Temp - Level High

Oil temperature higher than 75°C (167°F)

-Limit the use of thruster to prevent temperature to rise.

-Check if the cooling pump is running and there is cooling water fl ow.

-Inspect seawater fi lter

-Verify that cooling pump is enabled in parameter 0301

10501.0.13

PHC Oil Temp - Open Circuit

Analog oil temp sensor open circuit

-Sensor not connected or wire break.

- Disconnect sensor and measure that sensor resistance value is in 

range 104ohm-147Kohm

-The wrong sensor is defi ned in parameter 0201

10501.0.16

PHC Oil Temp - Short Circuit

Analog oil temp input short circuit

-Input shorted to GND, check wiring/sensor

-Disconnect sensor and measure that sensor resistance value is in 

range 104ohm-147Kohm

10502.0.13

PHC Stablizier Pressure - Open Circuit

Stabilizer pressure sensor open circuit

-Sensor not connected or wire break.

-System incorrectly confi gured with stabilizer, parameter 1001  

-Replace sensor

10502.0.16

PHC Stablizier Pressure - Short Circuit

Stabilizer pressure sensor short circuit

-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor

10502.0.19

PHC Stablizier Pressure - Under Limit

Stabilizer pressure has dropped below 20bar.

-Check accumulator charge pressure

-Check PTO pressure (if PTO powered)

-Check system for oil leaks

10502.0.20

PHC Stablizier Pressure - Over Limit

Stabilizer pressure is higher than:

set point + 30bar running from PTO

or set point + 15bar running from AC motor

-Check PTO pressure setting

-Check accumulator charge pressure

10502.0.26

PHC Stablizier Pressure - VALUE MAX

Stabilizer pressure reached sensor max value.

-Check that the correct sensor is fi tted

-Check that sensor range parameter 1010 match the sensor

-Check PTO pressure setting

10502.0.200 PHC Stablizier Pressure - Timeout

Stabilizer pressure has not reached 50% of setpoint parame-

ter 1003 after 30sec.

-Check the   pump feed shutoff  valve.

-Check PTO pressure (if PTO powered)

-Check system for oil leaks

10503.0.13

PHC System Pressure - Open Circuit

System pressure sensor open circuit

-Sensor not connected or wire break.

-Verify system pressure, parameter 0104

10503.0.16

PHC System Pressure - Short Circuit

System pressure sensor short circuit

-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor

10504.0.13

PHC AI 1 - Open Circuit

Analog Input 1 (4-20mA) sensor open circuit

-Sensor not connected or wire break.

10504.0.16

PHC AI 1 - Short Circuit

Analog Input 1 (4-20mA) sensor short circuit

-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor

10505.0.13

PHC AI 2 - Open Circuit

Analog Input 2 (4-20mA) sensor open circuit

-Sensor not connected or wire break.

10505.0.16

PHC AI 2 - Short Circuit

Analog Input 2 (4-20mA) sensor short circuit

-Wires shorted or sensor defective, check wiring/sensor

-Replace sensor

10508.0.13

PHC DOUT AC PUMP UNLOAD - Open Circuit AC Pump Unload valve open circuit

-Check for open circuit, power consumption < 5.0 Watt

-System incorrectly confi gured with stabilizer, parameter 1001

10508.0.51

PHC DOUT AC PUMP UNLOAD - Current High AC Pump Unload valve current higher than 4.0A

-Check wires and connections for short circuit

10509.0.13

PHC DOUT ACCUMULATOR DUMP - Open 

Circuit

Accumulator Dump valve open circuit

-Check for open circuit, power < 5.0 Watt

-System incorrectly confi gured with stabilizer, parameter 1001

10509.0.51

PHC DOUT ACCUMULATOR DUMP - Current 

High

Accumulator Dump valve current higher than 4.0A

-Check wires and connections for short circuit

10510.0.13

PHC DOUT STABILIZER - Open Circuit

Stabilizer valve open circuit

-Check for open circuit, power consumption  < 5.0 Watt

-System incorrectly confi gured with stabilizer, parameter 1001

10510.0.51

PHC DOUT STABILIZER - Current High

Stabilizer valve current higher than 4.0A

-Check wires and connections for short circuit

10511.0.13

PHC DOUT COOLING PUMP HYDRAULIC - 

Open Circuit

Hydraulic Cooling Pump valve open circuit

-Check for open circuit, power consumption  < 5.0 Watt

-Wrong cooling pump confi gured, parameter 0301

10511.0.51

PHC DOUT COOLING PUMP HYDRAULIC - 

Current High

Hydraulic Cooling Pump valve current higher than 4.0A

-Check wires and connections for short circuit

10512.0.13

PHC DOUT LS DUMP - Open Circuit

LS-Dump valve open circuit

-Check for open circuit, power consumption  < 5.0 Watt

-System wrong confi gured with thrusters, parameter 2001 or 2101

10512.0.51

PHC DOUT LS DUMP - Current High

LS-Dump valve current higher than 4.0A

-Check wires and connections for short circuit

10513.0.51

PHC DOUT PUMP #2 - Current High

Pump #2 valve current higher than 4.0A

-Check wires and connections for short circuit

10514.0.13

PHC DOUT 5 - Open Circuit

Digital Output 5 is confi gured as crossover and output is open 

circuit

-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0505

10514.0.51

PHC DOUT 5 - Current High

Digital Output 5 current higher than 4.0A

-Check wires and connections for short circuit

10515.0.13

PHC DOUT 6 - Open Circuit

Digital Output 6 is confi gured as crossover and output is open 

circuit

-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0506

10515.0.51

PHC DOUT 6 - Current High

Digital Output 6 current higher than 4.0A

-Check wires and connections for short circuit

10516.0.13

PHC DOUT 3 - Open Circuit

Digital Output 3 is confi gured as crossover and output is open 

circuit

-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0503

10516.0.51

PHC DOUT 3 - Current High

Digital Output 3 current higher than 4.0A

-Check wires and connections for short circuit

PHC-3 Alarm Descriptions

EN

MC_0117

Fault Code

Description

Cause

Action

10517.0.13

PHC DOUT 2 - Open Circuit

Digital Output 2 is confi gured as crossover and output is open 

circuit

-Check for open circuit, power consumption < 5.0 Watt

-Output confi gured wrong, parameter 0502

10517.0.51

PHC DOUT 2 - Current High

Digital Output 2 current higher than 4.0A

-Check wires and connections for short circuit

10518.0.13

PHC DOUT 1 - Open Circuit

Digital Output 1 is confi gured as crossover and output is open 

circuit

-Check for open circuit, power consumption  < 5.0 Watt

-Output confi gured wrong, parameter 0501

10518.0.51

PHC DOUT 1 - Current High

Digital Output 1 current higher than 4.0A

-Check wires and connections for short circuit

10519.0.13

PHC DOUT 4 - Open Circuit

Digital Output 4 is confi gured as crossover and output is open 

circuit

-Check for open circuit, power consumption < 5.0 Watt

-Output confi gured wrong, parameter 0504

10519.0.51

PHC DOUT 4 - Current High

Digital Output 4 current higher than 4.0A

-Check wires and connections for short circuit

10520.0.51

PHC ECI PUMP POWER FEED - Current High

ECI cooling pump power current higher than 8.0A

-Check pump cable for damage and short circuits

-Make sure the connector on the cooling pump is correctly inserted.

-Replace cooling pump

10521.0.51

PHC Bow Thruster Power - Current High

Bow thruster PVG feed current higher than 3.0A

-Check PVG wires and connections for short circuit

10522.0.51

PHC Stern Thruster Power - Current High

Stern thruster PVG feed current higher than 3.0A

-Check PVG wires and connections for short circuit

10523.0.51

PHC Thruster Power - Current High

Bow or Stern PVG feed current higher than 3.3A

Check all bow and stern PVG signal wires for short circuits

10524.0.51

PHC ECI Cooling Pump - Current High

ECI cooling pump current higher than 13.0A

-Check ECI cooling pump cable for damage and short circuits

-Replace ECI cooling pump

10524.0.53

PHC ECI Cooling Pump - Overvoltage

ECI cooling pump overvoltage, voltage higher than 33.0V

-Check PHC-3 input voltage is below 33.0V

-Replace ECI cooling pump

10524.0.54

PHC ECI Cooling Pump - Undervoltage

ECI cooling pump under voltage, voltage is lower than 18.0V

-Check PHC-3 input voltage is higher than 18.0V

-Replace ECI cooling pump

10524.0.55

PHC ECI Cooling Pump - Overtemp

ECI cooling pump temperature higher than 100°C (212°F)

-Check ECI cooling pump for damages

-Replace ECI cooling pump

10524.0.100 PHC ECI Cooling Pump - No Communication

No communication with ECI cooling pump

-Check if ECI pump is connected

-Check wires to ECI pump for open circuits

-Check power supply cooling pump

-Wrong cooling pump confi gured, parameter 0301

10524.0.205 PHC ECI Cooling Pump - HW FAULT

ECI cooling pump hardware fault

-Replace ECI cooling pump

10526.0.0

PHC ECI Cooling Pump Blocked - -

ECI cooling pump is blocked

-Reset fault and if fault reappears, cooling pump need service or 

replacement.

-Check pump inlet for obstacles

10527.1.0

PHC VFD Not Ready Instance 1 -

VFD not ready

-VFD external run enable/power available signal is lost.

10528.1.10

PHC VFD ABB Parameter Instance 1 Level Low ABB ACS550 parameter values 2001 or 2002 cannot be a 

negative value.

-Check ABB ACS550 parameter 2001 and 2002.

10529.0.19

PHC ECI Cooling Pump Speed - Under Limit

ECI pump motor speed under limit, below 100rpm

-Check hose for dirt

-Check pump inlet for obstacles

10530.0.201 PHC PTO ENGINE INSTANCE - INIT FAIL

Parameter 1011-PTO ENGINE INSTANCE is not defi ned

-Set parameter 1011-PTO ENGINE INSTANCE

36000.1.24

ABB ACS550 Instance 1 Fault

ABB ACS550 fault

See ABB ACS550 drive for more details

36002.1.24

VACON Instance 1 Fault

VACON VFD Fault

See VACON drive for more details

36100.1.100 VFD Instance 1 No Communication

Lost communication with VFD

-VFD not powered up

-VFD communication cable not connected or incorrectly wired

36103.1.0

VFD IN LOCAL Instance 1 -

VFD in local mode

-Switch VFD to remote mode

PDC-301 Alarm Descriptions

EN

MC_0119

Fault Code

Description

Cause

Action

10600.0.208

SR150000 Fault - INTERLOCK

Retract Interlock

-Check if retract is depoyed.

-No communication with Retract Controller, check Retract Controller 

has power.

-Check PDC-301 and Restract Controller setup.

36100.1.24

VFD Instance 1 Fault

VFD faulted

-See VFD for more information

36100.1.100 VFD Instance 1 No Communication

PDC-301 has no MODBUS communication with VFD.

-Check communication cable with VFD

-Check if VFD has power

36101.1.200 VFD PMS Instance 1 Timeout

VFD is not ready within 60 after power reqest.

-Check if VFD has power

36101.1.204 VFD PMS Instance 1 SIGNAL LOST

Lost Power Management signal from VFD, VFD not avilable 

anymore.

-Check VFD for more information.

36103.1.0

VFD IN LOCAL Instance 1 -

VFD in Local or Hand Mode

-Change mode in VFD panel.

Summary of Contents for S-linkControl Panel PJC221

Page 1: ...SLEIPNER MOTOR AS P O Box 519 N 1612 Fredrikstad Norway www side power com Document id Revision Date 3059 10 Control Panels PJC 221 PJC 222 To download your language go to www side power com K e e p t...

Page 2: ...System PDC 101 Setup 10 AC System PDC 201 Setup 10 AC System PDC 301 Setup 11 DC System Automatic Main Switch Setup 12 DC System PPC SR150000 SR61242 Setup 12 DC System RCRS 1 RCRS 2 Setup 13 DC Syste...

Page 3: ...ing to international or special national regulations Instructions in this guide cannot be guaranteed to comply with global electric mechanic regulations classification rules It is the installers respo...

Page 4: ...he direction of the arrows at select ed power Press for more and for less power 6 steps If any control unit are running the thruster in opposite direction to the hold function the hold function will b...

Page 5: ...EN 60533 Weight 215 gr Description Minimum Maximum Units Comment Input voltage 9 31 Volt DC Powered from S Link Current Voltage 20 120 mA External Alarm Buzzer Voltage 31 Volt DC External Alarm Buzzz...

Page 6: ...222 Supply 12V 24V DC S link External alarm buzzer 12V 24V DC max 0 5A Internal fuse relay External alarm buzzer connection Rear side of panel Connections for optional external buzzer audible alarm C...

Page 7: ...s can not be operated to auto setup is completed OR RUN SETUP DEVICES IN CONFLICT Detected devices in con ict Two or more thrusters defined as same instance bow stern bow STB Stern STB Run Setup proce...

Page 8: ...lve Pump Control will then not be able to edit NB Pump Control Auto must only be used on PHC 024 with rmware V 1 008 or higher Cooling Pump Values Always Running Temp Controlled default When the optio...

Page 9: ...o protect the thruster during deceleration and will close while thruster is running By selecting with Bypass Valve you activate this signal and addition change ramp parameters to match this setup All...

Page 10: ...display and thruster s at the right side of the display Direction Values NA Not Available AC System PDC 101 Setup AC System PDC 201 Setup EN EN MC_0096 MC_0096 PDC 201 Location Values BOW STERN BOW ST...

Page 11: ...uster location should be set as BOW STB or STERN STB This so the hydraulic controller are shown at the left side in display and thruster s at the right side of the display Direction Values Normal defa...

Page 12: ...his so the hydraulic controller are shown at the left side in display and thruster s at the right side of the display Direction Values Normal default Inverted Switches between Normal and Inverted runn...

Page 13: ...t sideways when both thrusters are operated simultanously with input from the remote only MSI8730 Location Values BOW STERN BOW STB STERN STB Set the location for selected device Use BOW or STERN in a...

Page 14: ...t of devices found can fill more than one screen A scroll bar indicates the position of the selected item The joystick s operates the thrusters as normal while info is displayed This will be useful fo...

Page 15: ...AN bus error status for the panel Showing no error and signal condition is good Example showing lots of error and very bad signal conditions DIAGNOSTIC DISPLAY Rx Error Count Receive error counter Err...

Page 16: ...CELSIUS Default FAHRENHEIT Set the panel temperature displaying unit WHEN RETRACT IS OUT Values NO WARNING Default WARNING EVERY 10sec Select WARNING EVERY 10sec for external buzzer or lamp warning ev...

Page 17: ...larm De scription pages in the Auto Reset column you can see which alarms that are auto reset SPECIFIC ALARMS STOP BUTTON Pressing the STOP button on a hydraulic panel will activate the dump valve and...

Page 18: ...shown in a dual stern thruster setup Battery indicator will be shown here in a single DC electric stern thruster setup BOW STERN BOW STB STERN STB Examples of display view for di erent panels applica...

Page 19: ...V thrusters Motor temperature indicator From 70 C 158 F to 130 C 266 F Symbol shown when a DC Thruster is used in a dual bow or dual stern setup Proportional Thruster Display Symbols EN MC_0053 Thrust...

Page 20: ...light in display and continous short beeps Voltage below 8 5V 15V 12V 24V system Temperature above 110 o C 230 o F None 4 Red backlight in display and continous short beeps If one or more of the thrus...

Page 21: ...Language English Backlight Level 5 Backlight Night Color Green Backlight Nightlevel 1 Timer Auto O 05 min Hold Calibration 70 Bow and Stern All system devices will be erased from memory Setup procedu...

Page 22: ...r 2 3 Motor relay fault Turn off thruster battery main switch Thruster must be serviced by author ized personel 8 Critical Error 2 3 PPC output fail PPC must be sent for service 9 Low Motor Current 2...

Page 23: ...1 2 3 Any Stabilizer alarm See stabilizer panel for more info 28 AC Motor Overtemp Yes 1 2 3 Hydraulic AC motor power pack over temp Higher than 120 C 248 F Stop running and wait for tempera ture to d...

Page 24: ...20mA sensor short circuit Wires shorted or sensor defective check wiring sensor Replace sensor 10505 0 13 PHC AI 2 Open Circuit Analog Input 2 4 20mA sensor open circuit Sensor not connected or wire b...

Page 25: ...0 55 PHC ECI Cooling Pump Overtemp ECI cooling pump temperature higher than 100 C 212 F Check ECI cooling pump for damages Replace ECI cooling pump 10524 0 100 PHC ECI Cooling Pump No Communication No...

Page 26: ...26 3059 10 2019 PJC 221 222 MC_0037 Notes EN...

Page 27: ...Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure easier Note Type...

Page 28: ...cument was correct at the time it was published However Sleipner Motor AS can not accept liability for any inaccuracies or omissions it may contain Continuous product improvement may change the produc...

Reviews: