PJC 221 & 222

Alarm Descriptions

EN

MC_0053

1. PPC520, PPC820, PPC800, PPC840

2. Buzzer is only activated when any device is sending thrust on the S-link bus. 

"Err.

No."

Errors shown in display "Auto

Reset"

"Ext. buzzer

activation at

Alert Level"

Description

Action

19

Actuator Fault

2

(

²

)

, 3

Actuator not getting any power

"Check actuator connection or pow-

er to actuator. Reset alarm in alarm 

menu on PJC 211/212/221/222 or 

recycle power."

20

Pos.Sensor Fault

2

(

²

)

, 3

Retract position sensor fail

Check position sensor cables and 

for sensor damage.

21

In Service Mode

Yes

2

(

²

)

, 3

"Retract controller in service mode. Switch 

no. 4 is ON."

Check dipswitch setting on retract 

control box.

22

High Oil Temp

Yes

1, 2

(

²

)

, 3

"Hydraulic oil temperature is higher than 

75°C /167°F."

"Stop running and wait for tempera-

ture to drop.

Check if cooling pump is running."

23

Low Oil Level

1, 2

(

²

)

, 3

Hydraulic oil lewel is to low

Fill more hydraulic oil to the hydrau-

lic tank.

24

Warning Return Filter

Yes

2

(

²

)

, 3

Return fi lter element requiered 

replacing.

25

Warning Pressure Filter

Yes

2

(

²

)

, 3

Pressure fi lter element requiered 

replacing.

26

Warning High Speed

Yes

1, 2

(

²

)

, 3

"WARNING! High Speed. 

Stabilizer not active!"

27

Stabilizer Fault

Yes

1, 2

(

²

)

, 3

Any Stabilizer alarm.

See stabilizer panel for more info.

28

AC Motor Overtemp

Yes

1, 2

(

²

)

, 3

"Hydraulic AC motor power pack over-

temp. Higher than

120°C/248°F."

Stop running and wait for tempera-

ture to drop.

29

AC Motor Sensor Fail

2

(

²

)

, 3

"Hydraulic AC motor power pack temp 

sensor open curicuit"

Check sensor cables.

30

Temperature Warning

Yes

2

(

²

)

, 3

(

²

)

High temperature warning.

Warns that the motor temperature is 

getting high.

31

Motor Overtemp

Yes

1, 2

(

²

)

, 3

High temperature Alarm.

See SAC manual for more details.

32

VFD Warning

Yes

2

(

²

)

, 3

There is an warning from VFD.

Check VFD for more details.

33

VFD Not Ready

Yes

2

(

²

)

, 3

The VFD is not ready.

Check VFD for more details.

34

VFD Fault

1, 2

(

²

)

, 3

VFD has an Alarm.

Check VFD for more details.

35

Warning Low Voltage

Yes

2

(

²

)

, 3

(

²

)

Low motor voltage warning when motor 

is running.

12V thruster below 9.30V

24V thruster below 17.50V

36

Not Calibrated

Yes

2

(

²

)

, 3

Shaft Not Calibrated

See manual for how to calibrate.

37

VFD Com. Fault

2

(

²

)

, 3

No Modbus communication with VFD

Check VFD Modbus cables and 

power.

38

Cooling Fan Fault  

2

(

²

)

, 3

Cooling fan stopped running, or running 

too slow

Device must be sent for service

39

Interlock

2

(

²

)

, 3

S-link communication between PPC and 

retract controller are missing

-Check PPC or retract controller has 

power.

-Check S-Link connections to PPC 

and retract controller.

-Check if not PPC or SR150000/

SR61242 is wrongly setup as SRP or 

SRVP/SRLP.

Alarm Descriptions

EN

MC_0053

1. PPC520, PPC820, PPC800, PPC840

2. Buzzer is only activated when any device is sending thrust on the S-link bus. 

"Err.

No."

Errors shown in display

"Auto

Reset"

"Ext. buzzer

activation at

Alert Level"

Description

Action

1

Motor Overcurrent

2

(

²

)

, 3

Motor current too high.

"Thruster must be serviced by author-

ized personnel, reset or power OFF/ON 

PPC

(

¹

)

."

2

Motor Overtemp

Yes

2

(

²

)

, 3

"Motortemp has been over 

120°C/248°F."

Motor cool down below 110°C /230°F.

3

Controller Overtemp

2

(

²

)

, 3

"PPC

(

¹

)

 temp has been over 

80°C/176°F."

PPC

(

¹

)

 cool down below 45°C/113°F.

4

Controller Overtemp

2

(

²

)

, 3

"SR150000 temp has been over 

80°C/176°F."

SR150000 cool down below 45°C 

/113°F.

5

Low Voltage

2

(

²

)

, 3

Low motor voltage alarm when motor 

is running.

12V thruster below 8.00V

24V thruster below 12.00V

Recharge battery, reset or power OFF/

ON  device.

6

Thermoswitch

Yes

2

(

²

)

, 3

Thermo switch input is activated and 

there is an open circuit.

The thruster needs to cool down before 

operating again.

7

IPC Error

2

(

²

)

, 3

Motor relay fault

"Turn off thruster battery main switch. 

Thruster must be serviced by author-

ized personel."

8

Critical Error

2

(

²

)

, 3

PPC

(

¹

)

 output fail

PPC

(

¹

)

 must be sent for service.

9

Low Motor Current

2

(

²

)

, 3

Thruster uses no power

Check thruster connections or motor 

dead!

10

Motor Contactor

2

(

²

)

, 3

No current on motor relay coil.

Check motor relay connections, short 

circuit or relay dead!

11

System Error

2

(

²

)

, 3

Fatal error

Device must be serviced by authorized 

personel

12

No Communication

2

(

²

)

, 3

No communication with device

Check S-Link cables and power con-

nections.

13

Motor Temp Sensor

2

(

²

)

, 3

Motor temperature sensor fail

Check for an open circuit on the temp 

sensor on the motor

14

Supply Voltage Fault

2

(

²

)

, 3

No power 

Check power connections

15

Fuse Blown

2

(

²

)

, 3

Fuse blown

Replace fuse or check if main cable 

from battery and main cable to thruster 

has been switched

16

Manual Override

Yes

2

(

²

)

, 3

Main switch manually overridden

Pull main switch

17

Motion OUT Fault

2

(

²

)

, 3

Retract obstructed while deploying

Turn off all panels. Go for lower speed/

deeper water and retry.

18

Motion IN Fault

2

(

²

)

, 3

Retract obstructed while retracting

Turn panel on and manually override 

main switch. Remove obstruction and 

try again.

Summary of Contents for S-linkControl Panel PJC221

Page 1: ...SLEIPNER MOTOR AS P O Box 519 N 1612 Fredrikstad Norway www side power com Document id Revision Date 3059 10 Control Panels PJC 221 PJC 222 To download your language go to www side power com K e e p t...

Page 2: ...System PDC 101 Setup 10 AC System PDC 201 Setup 10 AC System PDC 301 Setup 11 DC System Automatic Main Switch Setup 12 DC System PPC SR150000 SR61242 Setup 12 DC System RCRS 1 RCRS 2 Setup 13 DC Syste...

Page 3: ...ing to international or special national regulations Instructions in this guide cannot be guaranteed to comply with global electric mechanic regulations classification rules It is the installers respo...

Page 4: ...he direction of the arrows at select ed power Press for more and for less power 6 steps If any control unit are running the thruster in opposite direction to the hold function the hold function will b...

Page 5: ...EN 60533 Weight 215 gr Description Minimum Maximum Units Comment Input voltage 9 31 Volt DC Powered from S Link Current Voltage 20 120 mA External Alarm Buzzer Voltage 31 Volt DC External Alarm Buzzz...

Page 6: ...222 Supply 12V 24V DC S link External alarm buzzer 12V 24V DC max 0 5A Internal fuse relay External alarm buzzer connection Rear side of panel Connections for optional external buzzer audible alarm C...

Page 7: ...s can not be operated to auto setup is completed OR RUN SETUP DEVICES IN CONFLICT Detected devices in con ict Two or more thrusters defined as same instance bow stern bow STB Stern STB Run Setup proce...

Page 8: ...lve Pump Control will then not be able to edit NB Pump Control Auto must only be used on PHC 024 with rmware V 1 008 or higher Cooling Pump Values Always Running Temp Controlled default When the optio...

Page 9: ...o protect the thruster during deceleration and will close while thruster is running By selecting with Bypass Valve you activate this signal and addition change ramp parameters to match this setup All...

Page 10: ...display and thruster s at the right side of the display Direction Values NA Not Available AC System PDC 101 Setup AC System PDC 201 Setup EN EN MC_0096 MC_0096 PDC 201 Location Values BOW STERN BOW ST...

Page 11: ...uster location should be set as BOW STB or STERN STB This so the hydraulic controller are shown at the left side in display and thruster s at the right side of the display Direction Values Normal defa...

Page 12: ...his so the hydraulic controller are shown at the left side in display and thruster s at the right side of the display Direction Values Normal default Inverted Switches between Normal and Inverted runn...

Page 13: ...t sideways when both thrusters are operated simultanously with input from the remote only MSI8730 Location Values BOW STERN BOW STB STERN STB Set the location for selected device Use BOW or STERN in a...

Page 14: ...t of devices found can fill more than one screen A scroll bar indicates the position of the selected item The joystick s operates the thrusters as normal while info is displayed This will be useful fo...

Page 15: ...AN bus error status for the panel Showing no error and signal condition is good Example showing lots of error and very bad signal conditions DIAGNOSTIC DISPLAY Rx Error Count Receive error counter Err...

Page 16: ...CELSIUS Default FAHRENHEIT Set the panel temperature displaying unit WHEN RETRACT IS OUT Values NO WARNING Default WARNING EVERY 10sec Select WARNING EVERY 10sec for external buzzer or lamp warning ev...

Page 17: ...larm De scription pages in the Auto Reset column you can see which alarms that are auto reset SPECIFIC ALARMS STOP BUTTON Pressing the STOP button on a hydraulic panel will activate the dump valve and...

Page 18: ...shown in a dual stern thruster setup Battery indicator will be shown here in a single DC electric stern thruster setup BOW STERN BOW STB STERN STB Examples of display view for di erent panels applica...

Page 19: ...V thrusters Motor temperature indicator From 70 C 158 F to 130 C 266 F Symbol shown when a DC Thruster is used in a dual bow or dual stern setup Proportional Thruster Display Symbols EN MC_0053 Thrust...

Page 20: ...light in display and continous short beeps Voltage below 8 5V 15V 12V 24V system Temperature above 110 o C 230 o F None 4 Red backlight in display and continous short beeps If one or more of the thrus...

Page 21: ...Language English Backlight Level 5 Backlight Night Color Green Backlight Nightlevel 1 Timer Auto O 05 min Hold Calibration 70 Bow and Stern All system devices will be erased from memory Setup procedu...

Page 22: ...r 2 3 Motor relay fault Turn off thruster battery main switch Thruster must be serviced by author ized personel 8 Critical Error 2 3 PPC output fail PPC must be sent for service 9 Low Motor Current 2...

Page 23: ...1 2 3 Any Stabilizer alarm See stabilizer panel for more info 28 AC Motor Overtemp Yes 1 2 3 Hydraulic AC motor power pack over temp Higher than 120 C 248 F Stop running and wait for tempera ture to d...

Page 24: ...20mA sensor short circuit Wires shorted or sensor defective check wiring sensor Replace sensor 10505 0 13 PHC AI 2 Open Circuit Analog Input 2 4 20mA sensor open circuit Sensor not connected or wire b...

Page 25: ...0 55 PHC ECI Cooling Pump Overtemp ECI cooling pump temperature higher than 100 C 212 F Check ECI cooling pump for damages Replace ECI cooling pump 10524 0 100 PHC ECI Cooling Pump No Communication No...

Page 26: ...26 3059 10 2019 PJC 221 222 MC_0037 Notes EN...

Page 27: ...Thruster AMS PPC etc Bow Bow STB Stern Stern STB Fill in the type location and serial numbers of the S link devices installed Keeping this as a reference will make the setup procedure easier Note Type...

Page 28: ...cument was correct at the time it was published However Sleipner Motor AS can not accept liability for any inaccuracies or omissions it may contain Continuous product improvement may change the produc...

Reviews: