Characteristic data of the digital inputs
Table 35: Characteristic data of the digital inputs “External input 1” and “External input 2”
Type
Switching
Switching behavior
Power to the input starts the assigned function, e.g. start read cycle.
Default setting in the device: logic not inverted (active high), debounce
time 10 ms
Properties
•
Opto-decoupled, reverse polarity protected
•
Can be wired with PNP output of a trigger sensor
Electrical values
Low: V
in
1)
≤ 2 V; I
in
2)
≤ 0.3 mA
High: 6 V ≤ V
in
≤ 30 V; 0.7 mA ≤ I
in
≤ 5 mA
1)
Input Voltage
2)
Input current
NOTE
Assign the functions for the external digital inputs in the device using a configuration
tool, e.g., the SOPAS ET configuration software.
13.3.9
Wiring digital outputs of the device in the CDM420-0006
Device = Lector64x = V2D64xx-xxxxYx (Y = A, B or S)
Device = Lector65x = V2D65xx-xxxxYx (Y = A, B or S)
Device
1
CDM420-0006
Load (e.g. PLC)
4
C
5
.
.
.
E
Result
D
13
GND
5
Shield
+24 V* (V
S
)
V
S
GND
V
out
Result
A
GND
B
1
2
1
For inductive load:
6
5
2
3
3
1
7
2
6
5
4
8
13
14
17
15
9
10
12
16
11
8
7
1
10
15
6
11
5
Figure 40: Wiring the digital outputs “Result 1” and “Result 2” of the device in the connection module CDM420-0006
NOTE
The two digital outputs “Result 3” and “Result 4” are not available in the CDM420-0006.
1
Device
2
Supply voltage V
S
3
Adapter cable (female connector, M12, 17-pin, A-coded/male connector, D-Sub-HD, 15-pin)
4
Load (e.g. PLC)
5
Output voltage V
out
6
With inductive load: see note
7
Connection module: female connector, D-Sub-HD, 15-pin
ANNEX
13
8016185/19E9/2020-10-21 | SICK
O P E R A T I N G I N S T R U C T I O N S | Lector64x/65x Flex, Lector65x Dynamic Focus
91