3.
Select the desired destination, enter a file name, and click on
OK
.
✓
The tag names are saved as a CSV file.
7.5
Configuring the network interfaces
7.5.1
Configuring Modbus connections
Approach
1.
In the main navigation pane, click
Configuration
.
2.
In the navigation pane under
Main module
, select the
Fieldbus
menu item.
3.
Activate the
Modbus server
option.
4.
In the
Max. number of connections
field, select the number of connections.
7.5.2
Configuring SLMP connections
Approach
1.
In the main navigation pane, click
Configuration
.
2.
In the navigation pane under
Main module
, select the
Fieldbus
menu item.
3.
Activate the
SLMP server
option.
4.
In the
Port
field, select the port.
7.5.3
Configuring the output data (routing to CPU)
Overview
The CPUc2 main module can receive up to 50 bytes of output data from a higher-level
control system. The actual data volume and contents depends on how the output data
are configured in the higher-level control system.
The configuration of the output data includes the following points:
•
Specifying the routing
•
Enter the tag names for the data received from the network
Approach
1.
In the main navigation pane, click
Configuration
.
2.
In the navigation pane under
Main module
>
Fieldbus
, select the
Routing to CPU
menu
item.
3.
Select a routing template and drag it onto a single byte or several bytes of the
output data block.
✓
The bits, bytes or data formats are available as inputs in the logic editor.
✓
Each bit, byte or data format inherits a default tag name from the routing.
4.
If required, edit the default tag name in the
Settings
tab.
Complementary information
Table 14: Colors of the bytes and bits of a record
Color
Meaning
Light blue
The byte or the bit is empty.
Blue
The byte or the bit is occupied. The relevant module, input or
output is configured in the hardware configuration of the safety
controller.
Gray
The byte or the bit is occupied. The relevant module, input or
output is not yet configured in the hardware configuration of the
safety controller.
7
CONFIGURATION
54
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact
8024589/2020-11-10 | SICK
Subject to change without notice