Table 35: Warnings
Bit
Description
0
Maximum speed exceeded.
1
Permissible internal LED current in the sensor system exceeded.
2 ... 5
Not supported.
6
The lower limit of the speed configured with attribute 1Bh has been undercut.
7
The upper limit of the speed configured with attribute 1Ch has been exceeded.
8
The lower limit of the acceleration configured with attribute 20h has been under‐
cut.
9
The upper limit of the acceleration configured with attribute 21h has been
exceeded.
10
The lower/upper limit of the position configured with attribute 16h or 17h has
been undercut/exceeded.
11 ... 12
Reserved
13
The lower/upper limit of the temperature configured with attribute 67h or 68h
has been undercut/exceeded.
14
The minimum/maximum supply voltage has been undercut/exceeded.
7.3.4
Error messages of the Allen Bradley control system
If the encoder is integrated in an Allen Bradley control system, certain error messages
may occur whose message text cannot be clearly assigned.
Figure 116: Example of an error message in RSLogix
The following error messages come from the RSLogix 5000 software.
Table 36: Error messages from the RSLogix 5000 software
Error code
Message
Possible cause
16#0108
Connection Request Error Connec‐
tion Type (Multicast/Unicast) not sup‐
ported.
b
Check whether the configuration
assembly (instance 100 of the
assembly object) is activated. If
so, check whether the configu‐
ration data in it is configured
correctly and completely (
7
TROUBLESHOOTING
110
O P E R A T I N G I N S T R U C T I O N S | AFS/AFM60 EtherNet/IP
8014213/1EF3/2021-12-08 | SICK