Figure 24: IP address assigned successfully
5.2.3
Freezing the assigned IP address
1.
Switch off encoder (supply voltage off).
2.
Set value “000” via the three address switches.
3.
Switch on encoder (supply voltage on).
Deactivating DHCP server
4.
Click on the encoder address line in the lower window area to activate the
Disable
BOOTP/DHCP
button.
5.
Click the
Disable BOOTP/DHCP
button to deactivate the encoder’s DHCP server.
Figure 25:
Disable BOOTP/DHCP
button
6.
If the button does not respond to this request, the
Disable BOOTP/DHCP
option can
alternatively be activated via the
Disable BootP/DHCP
menu option under
Tools
.
CONFIGURATION USING A PLC
5
8014213/1EF3/2021-12-08 | SICK
O P E R A T I N G I N S T R U C T I O N S | AFS/AFM60 EtherNet/IP
49