Decreasing scaling of the analog output (non-safety-related function)
Setting
Description
4 mA
•
With the
4 mA
setting, the distance value to
be output with 4 mA at the analog output
can be set manually in millimeters.
•
The Teach function can be used to teach in
for the
4 mA … 20 mA
output function the
current distance value for an analog output
of 4 mA for the measured value.
20 mA
•
With the
20 mA
setting, the distance value to
be output with 20 mA at the analog output
can be set manually in millimeters.
•
The Teach function can be used to teach in
for the
4 mA … 20 mA
output function the
current distance value for an analog output
of 20 mA for the measured value.
Example analog output parameterization for Q2:
1.
Connect to the device and switch to the
Outputs settings
page in SOPAS ET.
2.
Set the Q2 switching function to
4 mA ... 20 mA
.
3.
Enter the distance to switching point 1 in the input window (optional: position the
object at switching point 1 and perform a
Teach
).
2)
4.
Enter the distance to switching point 2 in the input window (optional: position the
object at switching point 2 and perform a
Teach
).
2)
5.
Transfer parameters the device using the “Write all parameters” button.
6.
Check whether the function works appropriately for the configured parameters!
2)
For a decreasing behavior, the distance for 20 mA must be smaller than the distance for 4 mA.