Further topics
•
"Protection against interference from systems in close proximity to each other",
page 33
•
7.6
Configuring muting
Overview
Muting is configured using the DIP switches 1 to 4 (row A) on the receiver of a single
system.
Depending on arrangement of the muting sensors, cross-muting or exit monitoring can
be configured and the safety light curtain protection can be temporarily bypassed. In
combination with partial blanking, the safety can be increased by having the topmost
beam (far from system plug) remain active during a valid muting condition. A muting
signal can be moved from the extension connection to the system connection.
Important information
NOTE
Muting is only configured on the receiver of a single system.
Prerequisites
•
SP2 system plug
Configuring muting
OFF
uncoded
code 1
code 2
rev.conf.
ON
1 2 3 4
O F F
1 2 3 4
O F F
1 2 3 4
O F F
1
O
N
2
A
B
C
D
1
2 3 4
O F F
Figure 58: DIP switch for muting on the SP2 system plug
Table 34: DIP switch and muting
DIP switch 1
(row A)
DIP switch 2
(row A)
DIP switch 3
(row A)
DIP switch 4
(row A)
Function
Off
Off
Off
Off
Muting deactivated
(delivery condition)
Off
On
Off
Off
Cross muting
CONFIGURATION
7
8021645/1EB0/2022-04-28 | SICK
O P E R A T I N G I N S T R U C T I O N S | deTec4
97
Subject to change without notice