GETTING STARTED…
4
175
8024172/V3-0/2021-01
Subject to change without prior notice.
Operating instructions | LABEL CHECKER P6XX
4.15.8
CDBF600 module setup
Please be informed that you must be a “Service” level user in order to access the CDF
module settings.
Please be informed that any changes applied will only be saved, if you have re-activated
the
button.
All inspection regions will be displayed after image processing is finished with a short
delay.
Proceed as follows:
1.
Set the CDF module to Gateway mode.
2.
Adjust the mode switch to Position 2.
PROFINET version to position 2 or 3 depending on PROFINET address.
3.
Configure the CDF module to “handshake” mode.
4.
Using SOPAS ET software set the “Communication mode” of the PROFINET
version to “Mode CDF600”.
Please be informed that the PROFINET versions of CDF module always communicate via
“handshake” mode.
The Label Checker will not allow the use of external input “EXT IN1” in the CDF module.
When using PLC, the following files are necessary:
GSDML file
Gateway operating mode CDF600-2 PROFINET
The following PLC function blocks are necessary:
S7 function bloc S7-1200/1500TIA
Handheld, non-SOPAS devices, PROFINET
S7 function bloc S7-300/ 400 step 7 V5.5 Handheld, non-SOPAS devices, PROFINET